800 kVA diesel generator set

800 kVA GENERATOR

JJP-M640GF — 800 kVA / 640 kW prime, 880 kVA / 704 kW standby. 1,155 A per phase at 400 V, 143.3 L/h at full load. FOB China quoted against the engine and alternator you specify.

See the Full Specification
Other ratings in this range 100 kVA150 kVA200 kVA250 kVA300 kVA375 kVA400 kVA500 kVA625 kVA800 kVA1000 kVA1500 kVAAll 50–1500 kVA

800 kVA Generator — JJP-M640GF

Prime (PRP)
800 kVA
640 kW at 0.8 PF
Unlimited hours, 10% overload for 1 h in 12
Standby (ESP)
880 kVA
704 kW at 0.8 PF
Loss of mains only, 200 h/yr

800 kVA is the prime rating on the nameplate, not a rounded-up figure — the frame maps exactly onto the requirement. 1500 rpm at 50 Hz, 1800 rpm at 60 Hz, three-phase four-wire, 0.8 power factor.

How Many Amps Is a 800 kVA Generator?

VoltagePhaseCurrent at 800 kVASuggested breaker frame
380 V3-phase1,215 A1,600 A
400 V3-phase1,155 A1,600 A
415 V3-phase1,113 A1,600 A
440 V3-phase1,050 A1,600 A
480 V3-phase962 A1,250 A
220 V1-phase3,636 Aspecial winding
240 V1-phase3,333 Aspecial winding

I = kVA × 1000 ÷ (√3 × V). Breaker sizing at 125% of the 400 V figure gives 1,443 A, which lands on a 2,000 A frame. At this current the run is normally busbar or 4 × 150 mm² copper per phase rather than a single cable; have the route sized by the installing electrician.

Fuel Consumption per Hour

LoadDiesel L/hUS gal/h
800 kVA / 640 kW (100%)143.3 L/h37.9
640 kVA / 512 kW (80%)114.6 L/h30.3
480 kVA / 384 kW (60%)86.0 L/h22.7
320 kVA / 256 kW (40%)57.3 L/h15.1
160 kVA / 128 kW (20%)28.7 L/h7.6

Based on ≤187 g/kWh at 835 g/L diesel density — the same basis used across this site, so the figures compare directly with our other ratings. Consumption tracks load almost linearly in this class. The exact curve for the engine finally fitted is issued with the test report.

Engine and Alternator on the 800 kVA Frame

BrandEngine modelRatingStandby outputCylinders
YuchaiYC6C1070-D311070 PS787 kW6-cyl

Coupled to a Faraday FD6A-4 alternator, with a Deep Sea DSE7320 MKII controller as standard and DSE8610 for parallel operation. The Yuchai figure above is the engine rating; it clears the 640 kW prime requirement with margin, which is the match we apply across the range (engine sized at 1.1–1.15× the alternator output). Weichai, Cummins, Perkins and Volvo equivalents in the same power band are available on request — tell us the brand your service network already stocks and we will confirm the model and the price against it.

What Can a 800 kVA Generator Power?

Industrial plant or steel mill
510–580 kW of connected load. Two 800 kVA sets in parallel are the usual configuration where the process cannot stop.
Data centre hall
55–70 racks at 10 kW each. N+1 or 2N arrangements are the norm, and the synchronising panel is specified with the order rather than retro-fitted.
Airport or rail facility
Terminal services, runway lighting and signalling on a standby bus, with the set held at low load for long periods.
Large hospital campus
400–520 beds across several buildings. Zone the load so a single set failure sheds only non-clinical circuits.
Desalination or large pumping station
High-voltage motors on soft start, sequenced. Confirm the largest motor against the set transient response before ordering.
Marine or shipyard shore power
Shore supply for vessels under repair, where load steps are frequent and the set runs unattended.

Frame, Weight and Installation

Overall dimensions and dry weight move with the engine and the alternator actually fitted, so we do not publish a single figure for this rating and then quote you a set that does not match it. The general arrangement drawing issued with your order carries the exact envelope, lifting points and centre of gravity for the configuration you buy.

What does not change is the site work. Allow clearance at the alternator end for cooling air, confirm canopy door swing on both long sides before siting, and cast a level concrete plinth rated for 1.5× the wet weight. At this rating the set is a crane lift in every configuration. Confirm the crane capacity against the GA drawing weight, and plan the route before the wall goes up.

Ask for the drawing for the engine you are considering — it is the only number worth designing a plant room around.

What Does a 800 kVA Generator Cost?

At this rating the engine and the alternator together account for most of the cost, and the band between a cost-competitive build and a premium build is wider than at the smaller frames. We quote this rating against the engine and alternator you specify rather than publishing a catalogue band. What we need to give you a firm number: running kW and the largest motor, the duty (standby, prime or continuous), the destination port, and whether you want open skid, silent canopy or container. From those we confirm the engine option, the tank size and the canopy grade, and price it landed-ready. A sound-attenuated canopy typically adds 8–12% and roughly 200–300 kg at this rating; a synchronising panel, an ATS and the breaker are priced separately because they depend on the switchboard you already have.

800 kVA Generator Questions

How many amps does a 800 kVA generator deliver?

1,155 A per phase at 400 V three-phase, 1,215 A at 380 V, 962 A at 480 V. Size the breaker at 125% of the 400 V figure: that gives 1,443 A, which lands on a 2,000 A frame.

What does a 800 kVA generator weigh?

Weight depends on the engine and alternator fitted, so we do not publish a single figure for this rating. The general arrangement drawing issued with your order carries the exact dry weight, the lifting points and the centre of gravity for the configuration you buy — ask for it for the engine you are considering before you design the plant room.

How much fuel does a 800 kVA generator use per hour?

About 143.3 L/h at full 640 kW load and 71.6 L/h at half load, on the ≤187 g/kWh basis used across this site. Consumption is close to linear with load in this class, so the fuel bill per kWh barely moves between 50% and 100% load.

Is 800 kVA the same as 640 kW?

At 0.8 power factor, yes — 800 × 0.8 = 640 kW. A lower site power factor reduces the usable kW further, so check the PF before confirming the rating.

What is the standby rating of this set?

880 kVA / 704 kW, which is 10% above prime. Standby is for loss of mains only and is rated at 200 hours a year; if the set runs as the main supply, specify it at prime instead.

Can two 800 kVA sets run in parallel?

Yes, with the DSE8610 controller, matching alternator pitch and a synchronising panel. Two sets give 1600 kVA total, or N+1 redundancy at 800 kVA. Specify it at the quote stage — retro-fitting is expensive.

Which engine brand should I choose?

The Yuchai YC6C1070-D31 is the configuration in our standard quotation for this rating. Weichai, Cummins, Perkins and Volvo equivalents in the same power band are available on request. Choose on parts availability where you operate: Cummins and Perkins have the widest network across Africa and the Middle East, Weichai and Yuchai are the cost-competitive options with strong regional support, Volvo suits projects with emission or brand requirements.

What noise level should I expect?

65–75 dB(A) at 7 m for a canopied set, depending on acoustic grade. Residential-grade units sit at the low end; standard export canopies at the high end. Open skid sets are not normally specified where noise matters.

Send the load schedule, get a firm FOB price

Running kW, largest motor, duty and destination port — we will confirm the engine option, the tank size and the canopy grade, and price it landed-ready.