Volvo Penta Powered Diesel Generator Sets
Each model lists the complete power chain: genset model standby / prime (kVA & kW) rated current genuine Volvo Penta engine with prime/standby kW Stamford alternator with kVA controller. Built on Volvo Penta TAD550–TWD1653 GE industrial engines.
| Genset Model | Genset Output @ 50 Hz | Engine | Alternator (Stamford) | Controller | |||
|---|---|---|---|---|---|---|---|
| StandbykVA / kW (ESP) | PrimekVA / kW (PRP) | CurrentA @ 400 V | Engine Model | Eng. P/Sprime / standby kW | |||
| 50–90 kW | |||||||
| JJV-80GF | 110kVA/88 kW | 100kVA/80 kW | 144.3 | TAD550GE Volvo | 76 / 84 | UCI274C 120 kVA | SmartGen HGM6110N |
| JJV-90GF | 124kVA/99.2 kW | 112kVA/90 kW | 162.4 | TAD551GE Volvo | 89 / 98 | UCI274D 135 kVA | SmartGen HGM6110N |
| 100–180 kW | |||||||
| JJV-112GF | 154kVA/123.2 kW | 140kVA/112 kW | 202.1 | TAD750GE Volvo | 113 / 127 | UCI274E 160 kVA | SmartGen HGM6110N |
| JJV-128GF | 176kVA/140.8 kW | 160kVA/128 kW | 230.9 | TAD752GE Volvo | 158 / 174 | UCI274G 180 kVA | SmartGen HGM6110N |
| JJV-160GF | 220kVA/176 kW | 200kVA/160 kW | 288.7 | TAD753GE Volvo | 175 / 194 | UCI274J 230 kVA | SmartGen HGM6110N |
| JJV-180GF | 248kVA/198.4 kW | 225kVA/180 kW | 324.8 | TAD754GE Volvo | 219 / 242 | UCD274K 250 kVA | SmartGen HGM6110N |
| 200–320 kW | |||||||
| JJV-200GF | 275kVA/220 kW | 250kVA/200 kW | 360.8 | TAD754GE Volvo | 219 / 242 | HCI444D 300 kVA | SmartGen HGM6110N |
| JJV-200GF | 275kVA/220 kW | 250kVA/200 kW | 360.8 | TAD754GE Volvo | 219 / 242 | HCI444D 300 kVA | SmartGen HGM6110N |
| JJV-220GF | 302kVA/241.6 kW | 275kVA/220 kW | 396.9 | TAD754GE Volvo | 219 / 242 | HCI444ES 325 kVA | SmartGen HGM6110N |
| JJV-280GF | 385kVA/308 kW | 350kVA/280 kW | 505.2 | TAD1351GE Volvo | 279 / 306 | HCI444F 400 kVA | SmartGen HGM6110N |
| JJV-300GF | 412kVA/329.6 kW | 375kVA/300 kW | 541.3 | TAD1352GE Volvo | 314 / 345 | HCI544C 500 kVA | SmartGen HGM6110N |
| JJV-320GF | 440kVA/352 kW | 400kVA/320 kW | 577.3 | TAD1354GE Volvo | 328 / 361 | HCI544C 500 kVA | SmartGen HGM6110N |
| 350–500 kW | |||||||
| JJV-350GF | 481kVA/384.8 kW | 438kVA/350 kW | 631.5 | TAD1355GE Volvo | 355 / 390 | HCI544C 500 kVA | SmartGen HGM6110N |
| JJV-350GF | 481kVA/384.8 kW | 438kVA/350 kW | 631.5 | TAD1355GE Volvo | 355 / 390 | HCI544C 500 kVA | SmartGen HGM6110N |
| JJV-400GF | 550kVA/440 kW | 500kVA/400 kW | 721.7 | TAD1650GE Volvo | 393 / 433 | HCI544D 550 kVA | SmartGen HGM6110N |
| JJV-440GF | 605kVA/484 kW | 550kVA/440 kW | 793.8 | TAD1651GE Volvo | 430 / 473 | HCI544E 610 kVA | SmartGen HGM6110N |
| JJV-500GF | 688kVA/550.4 kW | 625kVA/500 kW | 902.1 | TWD1652GE Volvo | 505 / 557 | HCI634G 810 kVA | SmartGen HGM6110N |
| 550–750 kW | |||||||
| JJV-550GF | 756kVA/604.8 kW | 688kVA/550 kW | 992.3 | TWD1653GE Volvo | 547 / 604 | HCI634G 810 kVA | SmartGen HGM6110N |
No model matches your filter. Try a shorter keyword or reset the filters.
Engines are sized with a power reserve over the alternator prime output (industry rule ≈ 1.05–1.22×). Every engine kW figure below is taken from the engine maker's published 1500 rpm / 50 Hz rating, not estimated.
Engine ratings: Volvo Penta official technical data. Alternator capacities: STAMFORD | AvK official ratings. Values for reference at ≤1000 m, ≤40 °C; final data follows the order contract.
Volvo Penta and Volvo CE industrial engines are the quietest and cleanest option in the 80–550 kW band. The TAD series meets EU Stage and EPA Tier emissions without after-treatment on most ratings, which matters in jurisdictions where a visible stack or a DEF tank is a planning problem.
If your noise limit is under 70 dB(A) at 7 m, or your permit requires a Tier 4 / Stage V engine, start here. The purchase price is higher than Weichai or SDEC at the same rating; the enclosure cost is usually lower because the engine is already quiet.
The table above lists Volvo genset ratings from 80–550 kW with the engine model, alternator frame and typical fuel consumption for each. Two columns decide most enquiries: the standby rating (what the set can carry for the duration of an outage) and the prime rating (what it can carry continuously). If you are comparing our table against another supplier's, check whether their figures are prime or standby — a standby rating quoted as prime is roughly 10 percent optimistic.
Jinjia Power is a diesel generator supplier and genset manufacturer in Dongguan, China, assembling every rating on this table in our own works and load-bank testing each unit at 100 percent rated output before shipment. Send the standby kVA you need, the voltage and frequency (50 or 60 Hz) and the destination port, and you get a firm quote inside one working day — engine model, alternator frame, controller, canopy grade and CIF price on one sheet. If the rating you need is not on the table, ask anyway: we build non-standard ratings as a normal option rather than a special order.
It lists 18 models from 88 kW to 604 kW standby, with prime ratings from 80 kW to 550 kW. The table carries the TAD and TWD industrial series.
Standby is emergency duty with a varying load and no overload. Prime allows a 10 per cent overload for one hour in twelve and is the number to quote for continuous supply. Across this table standby averages about 1.10 times prime, so the same physical set carries two different numbers. Always state which one you are specifying against, because the price and the warranty follow the rating.
It is full-load line current at 400 V three phase, derived from the standby kVA: kVA times 1000 divided by root three times 400. Use it directly for cable and breaker sizing, then apply the derating for the ambient temperature and the installation method on site.
The engine carries the alternator losses as well as the electrical load. On this table the margin runs from about 1.05 to 1.22 times depending on the frame. An engine matched exactly to the alternator rating has nothing left for altitude, high ambient or a heavy direct-on-line motor start.
1000 m altitude or below and 40 degrees C ambient, taken from the engine maker's and the alternator maker's published catalogues. Above that the set derates by roughly 1 per cent per 100 m and 2 to 3 per cent per 5 degrees C. Send the site conditions with the enquiry and the quoted figure will be the derated one.
SmartGen HGM420N on the smaller frames and HGM6110N or HGM6120N from roughly 100 kW upward. The controller is a specification item, not fixed — Deep Sea, ComAp or a specific paralleling panel can be built instead if the project standard names one.
Because Volvo Penta builds industrial engines for a defined band rather than the full spread. This table covers 80 to 550 kW prime in 18 models. Below that the Volvo option is uneconomic against a Perkins or SDEC build, and above it the answer is normally a Mitsubishi, MTU or a Cummins CCEC frame. We would rather say that than stretch a small engine past its duty.
TAD is the smaller industrial family and TWD the larger, heavier one, both turbocharged and aftercooled. The TWD frames in this table run up to 550 kW prime. Both are the industrial range rather than the marine range, so the ratings are continuous-duty industrial figures rather than pleasure-craft figures.
Yes. The table is the commonly built range. Different voltages, 60 Hz builds, marine duty engines, silent canopies, container packages and dual-bearing alternators are all normal variations. Give the duty, the site conditions and the voltage and the closest frame is quoted with the deviation listed.
Standard frames ship in 3 to 7 working days from the factory for a single set, longer for a containerised or paralleling package. There is no minimum order for a single genset. Sets leave from Shenzhen or Guangzhou port, and the export terms are normally 30 per cent deposit with the balance before shipment.