Home › Volvo Generators › Technical Selection Table

Volvo Penta Powered Diesel Generator Sets

Volvo Genset Technical Selection Table — TAD / TWD Series

Each model lists the complete power chain: genset model standby / prime (kVA & kW) rated current genuine Volvo Penta engine with prime/standby kW Stamford alternator with kVA controller. Built on Volvo Penta TAD550–TWD1653 GE industrial engines.

18standard models 80–550 kWprime range 50 Hz / 1500 rpm400/230 V, PF 0.8 Volvo Penta + Stamfordgenuine brands
Genset Model Genset Output @ 50 Hz Engine Alternator (Stamford) Controller
StandbykVA / kW (ESP) PrimekVA / kW (PRP) CurrentA @ 400 V Engine Model Eng. P/Sprime / standby kW
50–90 kW
JJV-80GF110kVA/88 kW100kVA/80 kW144.3
TAD550GE
Volvo
76 / 84
UCI274C
120 kVA
SmartGen HGM6110N
JJV-90GF124kVA/99.2 kW112kVA/90 kW162.4
TAD551GE
Volvo
89 / 98
UCI274D
135 kVA
SmartGen HGM6110N
100–180 kW
JJV-112GF154kVA/123.2 kW140kVA/112 kW202.1
TAD750GE
Volvo
113 / 127
UCI274E
160 kVA
SmartGen HGM6110N
JJV-128GF176kVA/140.8 kW160kVA/128 kW230.9
TAD752GE
Volvo
158 / 174
UCI274G
180 kVA
SmartGen HGM6110N
JJV-160GF220kVA/176 kW200kVA/160 kW288.7
TAD753GE
Volvo
175 / 194
UCI274J
230 kVA
SmartGen HGM6110N
JJV-180GF248kVA/198.4 kW225kVA/180 kW324.8
TAD754GE
Volvo
219 / 242
UCD274K
250 kVA
SmartGen HGM6110N
200–320 kW
JJV-200GF275kVA/220 kW250kVA/200 kW360.8
TAD754GE
Volvo
219 / 242
HCI444D
300 kVA
SmartGen HGM6110N
JJV-200GF275kVA/220 kW250kVA/200 kW360.8
TAD754GE
Volvo
219 / 242
HCI444D
300 kVA
SmartGen HGM6110N
JJV-220GF302kVA/241.6 kW275kVA/220 kW396.9
TAD754GE
Volvo
219 / 242
HCI444ES
325 kVA
SmartGen HGM6110N
JJV-280GF385kVA/308 kW350kVA/280 kW505.2
TAD1351GE
Volvo
279 / 306
HCI444F
400 kVA
SmartGen HGM6110N
JJV-300GF412kVA/329.6 kW375kVA/300 kW541.3
TAD1352GE
Volvo
314 / 345
HCI544C
500 kVA
SmartGen HGM6110N
JJV-320GF440kVA/352 kW400kVA/320 kW577.3
TAD1354GE
Volvo
328 / 361
HCI544C
500 kVA
SmartGen HGM6110N
350–500 kW
JJV-350GF481kVA/384.8 kW438kVA/350 kW631.5
TAD1355GE
Volvo
355 / 390
HCI544C
500 kVA
SmartGen HGM6110N
JJV-350GF481kVA/384.8 kW438kVA/350 kW631.5
TAD1355GE
Volvo
355 / 390
HCI544C
500 kVA
SmartGen HGM6110N
JJV-400GF550kVA/440 kW500kVA/400 kW721.7
TAD1650GE
Volvo
393 / 433
HCI544D
550 kVA
SmartGen HGM6110N
JJV-440GF605kVA/484 kW550kVA/440 kW793.8
TAD1651GE
Volvo
430 / 473
HCI544E
610 kVA
SmartGen HGM6110N
JJV-500GF688kVA/550.4 kW625kVA/500 kW902.1
TWD1652GE
Volvo
505 / 557
HCI634G
810 kVA
SmartGen HGM6110N
550–750 kW
JJV-550GF756kVA/604.8 kW688kVA/550 kW992.3
TWD1653GE
Volvo
547 / 604
HCI634G
810 kVA
SmartGen HGM6110N

No model matches your filter. Try a shorter keyword or reset the filters.

Power definitions (ISO 8528)

  • PRP (Prime) — unlimited-hours base power; 10% overload for 1 h in every 12 h.
  • ESP (Standby) — emergency maximum, no overload (typically +10% over prime).
  • Rated current I = Prime kW / (√3 × 400 V), three-phase PF 0.8.

Engine-to-set matching

Engines are sized with a power reserve over the alternator prime output (industry rule ≈ 1.05–1.22×). Every engine kW figure below is taken from the engine maker's published 1500 rpm / 50 Hz rating, not estimated.

Configuration & options

  • Alternator: genuine Stamford, brushless, H-class, IP23, PF 0.8.
  • Controller: SmartGen HGM series standard; Deep Sea DSE6120/7320 on request.
  • Open / silent / super-silent / trailer types; ATS, parallel & remote-monitoring optional.

Data sources

Engine ratings: Volvo Penta official technical data. Alternator capacities: STAMFORD | AvK official ratings. Values for reference at ≤1000 m, ≤40 °C; final data follows the order contract.

Need a quoted datasheet or custom configuration?
Tell us the required kW, standby/base use and sound level — we reply with factory price & specs.