Home › SDEC Generators › Technical Selection Table

SDEC (Shanghai Diesel) Powered Generator Sets

SDEC Genset Technical Selection Table — 60 to 3000 kW

Every model lists the complete power chain: genset model standby / prime (kVA & kW) rated current genuine SDEC engine with prime/standby kW Stamford alternator with kVA controller, plus displacement, cylinders, noise, weight and dimensions.

37standard models 60–3000 kWprime range 50 Hz / 1500 rpm400/230 V, PF 0.8 SDEC + Stamfordgenuine brands
Genset Model Genset Output @ 50 Hz Engine Alternator (Stamford) Controller Mechanical Data
StandbykVA / kW (ESP) PrimekVA / kW (PRP) CurrentA @ 400 V Engine Model Eng. P/Sprime / standby kW Displ.LNoisedB(A) @7mWeight / Dims.
50–90 kW
KDGS66S83kVA/66.4 kW75kVA/60 kW108.3
4ZTAA3.5-G31
SDEC
74 / 81
UCI224G
85 kVA
SmartGen HGM6110N3.50≤85790 kg
1850×700×1300
KDGS70S87kVA/69.6 kW80kVA/64 kW115.5
4HTAA4.3-G33
SDEC
78 / 86
UCI274C
120 kVA
SmartGen HGM6110N4.30≤921050 kg
1950×900×1200
KDGS90S113kVA/90.4 kW100kVA/80 kW144.3
4HTAA4.3-G34
SDEC
95 / 105
UCI274C
120 kVA
SmartGen HGM6110N4.30≤921100 kg
1950×950×1200
KDGS100S125kVA/100 kW112kVA/89.6 kW161.7
4HTAA4.3-G35
SDEC
106 / 117
UCI274D
135 kVA
SmartGen HGM6110N4.30≤921110 kg
1950×950×1200
100–180 kW
KDGS120S150kVA/120 kW137kVA/109.6 kW197.7
4HTAA4.3-G36
SDEC
120 / 132
UCI274E
160 kVA
SmartGen HGM6110N4.30≤921150 kg
1950×950×1200
KDGS132S165kVA/132 kW150kVA/120 kW216.5
6HTAA6.5-G32
SDEC
140 / 155
UCI274G
180 kVA
SmartGen HGM6110N4.30≤951360 kg
2350×950×1375
KDGS150S187kVA/149.6 kW150kVA/120 kW216.5
6HTAA6.5-G35
SDEC
155 / 170
UCI274H
200 kVA
SmartGen HGM6110N4.30≤951360 kg
2350×950×1375
KDGS165S206kVA/164.8 kW187kVA/149.6 kW269.9
6HTAA6.5-G33
SDEC
168 / 185
UCI274J
230 kVA
SmartGen HGM6110N4.30≤951410 kg
2320×950×1375
KDGS180S225kVA/180 kW200kVA/160 kW288.7
6HTAA6.5-G34
SDEC
186 / 205
UCI274J
230 kVA
SmartGen HGM6110N4.30≤951440 kg
2320×950×1375
KDGS200S250kVA/200 kW225kVA/180 kW324.8
6DTAA8.9-G32
SDEC
208 / 228
UCD274K
250 kVA
SmartGen HGM6110N8.82≤961830 kg
2550×1000×1385
200–320 kW
KDGS220S275kVA/220 kW250kVA/200 kW360.8
6DTAA8.9-G33
SDEC
230 / 253
HCI444D
300 kVA
SmartGen HGM6110N8.82≤961950 kg
2550×1000×1470
KDGS250S312kVA/249.6 kW275kVA/220 kW396.9
6DTAA8.9-G34
SDEC
245 / 253
HCI444ES
325 kVA
SmartGen HGM6110N8.82≤961950 kg
2550×1000×1470
KDGS280S350kVA/280 kW312kVA/249.6 kW450.3
6ETAA11.8-G32
SDEC
280 / 308
HCI444E
350 kVA
SmartGen HGM6110N11.82≤972800 kg
3000×1250×1620
KDGS300S375kVA/300 kW350kVA/280 kW505.2
6ETAA11.8-G33
SDEC
307 / 338
HCI444FS
380 kVA
SmartGen HGM6110N11.82≤972550 kg
3100×1150×1620
KDGS330S412kVA/329.6 kW375kVA/300 kW541.3
6ETAA11.8-G31
SDEC
340 / 380
HCI544C
500 kVA
SmartGen HGM6110N11.82≤972800 kg
2950×1150×1620
KDGS360S450kVA/360 kW400kVA/320 kW577.3
6ETAA12.8-G32
SDEC
360 / 400
HCI544C
500 kVA
SmartGen HGM6110N12.82≤972700 kg
3100×1150×1620
350–500 kW
KDGS400S500kVA/400 kW450kVA/360 kW649.5
6ETAA12.8-G31
SDEC
401 / 441
HCI544C
500 kVA
SmartGen HGM6110N12.82≤972700 kg
3300×1150×1620
KDGS440S550kVA/440 kW500kVA/400 kW721.7
6ETAA12.8-G310
SDEC
450 / 495
HCI544D
550 kVA
SmartGen HGM6110N12.82≤973100 kg
3100×1300×1770
KDGS500S625kVA/500 kW562kVA/449.6 kW811.2
12GTAA27-G33
SDEC
505 / 555
HCI544FS
625 kVA
SmartGen HGM6110N26.60≤1034370 kg
3550×1690×2120
KDGS550S687kVA/549.6 kW625kVA/500 kW902.1
12GTAA27-G32
SDEC
565 / 622
HCI634G
810 kVA
SmartGen HGM6110N26.60≤1034550 kg
3400×1690×2120
550–750 kW
KDGS620S750kVA/600 kW700kVA/560 kW1010.3
12GTAA27-G31
SDEC
622 / 684
HCI634G
810 kVA
SmartGen HGM6110N26.60≤1034550 kg
3400×1690×2120
KDGS660S825kVA/660 kW750kVA/600 kW1082.5
6KTAA25-G32
SDEC
685 / 754
HCI634H
940 kVA
SmartGen HGM6110N25.20≤1125550 kg
3800×1640×2160
KDGS720S900kVA/720 kW825kVA/660 kW1190.8
6KTAA25-G31
SDEC
728 / 800
HCI634H
940 kVA
SmartGen HGM6110N25.20≤1125650 kg
3900×1640×2160
KDGS800S1000kVA/800 kW900kVA/720 kW1299
6KTAA25-G320
SDEC
820 / 902
S6L1D-C
1000 kVA
SmartGen HGM6110N25.20≤1126050 kg
4000×1750×2320
800–1000 kW
KDGS900S1125kVA/900 kW1000kVA/800 kW1443.3
6KTAA25-G321
SDEC
880 / 968
S6L1D-D
1125 kVA
SmartGen HGM6110N25.20≤1126250 kg
4000×1750×2320
KDGS1000S1250kVA/1000 kW1125kVA/900 kW1623.8
6WTAA35-G310
SDEC
1018 / 1120
S6L1D-E
1250 kVA
SmartGen HGM6110N35.10≤1188000 kg
4500×2080×2450
KDGS1100S1375kVA/1100 kW1250kVA/1000 kW1804.2
6WTAA35-G311
SDEC
1118 / 1230
S6L1D-F
1400 kVA
SmartGen HGM6110N35.10≤1188050 kg
4500×2080×2450
1100–1500 kW
KDGS1200S1500kVA/1200 kW1375kVA/1100 kW1984.6
12KTA58-G36
SDEC
1280 / 1410
S7L1D-C4
1550 kVA
SmartGen HGM6120N57.20≤11513550 kg
4500×2200×2515
KDGS1350S1688kVA/1350.4 kW1563kVA/1250.4 kW2255.9
12KTA58-G35
SDEC
1420 / 1560
S7L1D-E4
1750 kVA
SmartGen HGM6120N57.20≤11513970 kg
4500×2200×2515
KDGS1500S1875kVA/1500 kW1688kVA/1350.4 kW2436.3
12KTA58-G34
SDEC
1560 / 1720
S7L1D-F4
1900 kVA
SmartGen HGM6120N57.20≤11514430 kg
4600×2200×2515
KDGS1650S2063kVA/1650.4 kW1875kVA/1500 kW2706.3
12KTA58-G33
SDEC
1720 / 1890
S7L1D-G4
2080 kVA
SmartGen HGM6120N57.20≤11514770 kg
4600×2200×2515
≥1600 kW
KDGS1800S2250kVA/1800 kW2000kVA/1600 kW2886.7
12KTA58-G32
SDEC
1850 / 2035
S7L1D-H4
2250 kVA
SmartGen HGM6120N57.20≤11515090 kg
4700×2200×2515
KDGS2000S2500kVA/2000 kW2250kVA/1800 kW3247.5
12KTA58-G31
SDEC
2010 / 2210
S7L1D-J4
2500 kVA
SmartGen HGM6120N57.20≤11515260 kg
4700×2455×2515
KDGS2200S2750kVA/2200 kW2500kVA/2000 kW3608.3
16KTA76-G33
SDEC
2250 / 2500
S7/P80/S9 series (factory-engineered)
2750 kVA
SmartGen HGM6120N76.30≤12218200 kg
6400×2560×2900
KDGS2400S3000kVA/2400 kW2750kVA/2200 kW3969.2
16KTA76-G32
SDEC
2510 / 2780
S7/P80/S9 series (factory-engineered)
3000 kVA
SmartGen HGM6120N76.30≤12218500 kg
6400×2560×2900
KDGS2600S3250kVA/2600 kW3000kVA/2400 kW4330
16KTA76-G31
SDEC
2680 / 2950
S7/P80/S9 series (factory-engineered)
3250 kVA
SmartGen HGM6120N76.30≤12218900 kg
6500×2830×2900
KDGS2800S3500kVA/2800 kW3125kVA/2500 kW4510.4
16KTA76-G310
SDEC
2773 / —
S7/P80/S9 series (factory-engineered)
3500 kVA
SmartGen HGM6120N76.30≤12219100 kg
6600×2830×3430

No model matches your filter. Try a shorter keyword or reset the filters.

Power definitions (ISO 8528)

  • PRP (Prime) — unlimited-hours base power; 10% overload for 1 h in every 12 h.
  • ESP (Standby) — emergency maximum, no overload (typically +10% over prime).
  • Rated current I = Prime kW / (√3 × 400 V), three-phase PF 0.8.

Engine-to-set matching

Engines are sized with a power reserve over the alternator prime output (industry rule ≈ 1.05–1.22×). Every engine kW figure below is taken from the engine maker's published 1500 rpm / 50 Hz rating, not estimated.

Configuration & options

  • Alternator: genuine Stamford, brushless, H-class, IP23, PF 0.8.
  • Controller: SmartGen HGM series standard; Deep Sea DSE6120/7320 on request.
  • Open / silent / super-silent / trailer types; ATS, parallel & remote-monitoring optional.

Data sources

Engine ratings: SDEC (Shanghai Diesel Engine) official catalogue. Alternator capacities: STAMFORD | AvK official ratings. Values for reference at ≤1000 m, ≤40 °C; final data follows the order contract.

Need a quoted datasheet or custom configuration?
Tell us the required kW, standby/base use and sound level — we reply with factory price & specs.