SDEC (Shanghai Diesel) Powered Generator Sets
Every model lists the complete power chain: genset model standby / prime (kVA & kW) rated current genuine SDEC engine with prime/standby kW Stamford alternator with kVA controller, plus displacement, cylinders, noise, weight and dimensions.
| Genset Model | Genset Output @ 50 Hz | Engine | Alternator (Stamford) | Controller | Mechanical Data | |||||
|---|---|---|---|---|---|---|---|---|---|---|
| StandbykVA / kW (ESP) | PrimekVA / kW (PRP) | CurrentA @ 400 V | Engine Model | Eng. P/Sprime / standby kW | Displ.L | NoisedB(A) @7m | Weight / Dims. | |||
| 50–90 kW | ||||||||||
| KDGS66S | 83kVA/66.4 kW | 75kVA/60 kW | 108.3 | 4ZTAA3.5-G31 SDEC | 74 / 81 | UCI224G 85 kVA | SmartGen HGM6110N | 3.50 | ≤85 | 790 kg 1850×700×1300 |
| KDGS70S | 87kVA/69.6 kW | 80kVA/64 kW | 115.5 | 4HTAA4.3-G33 SDEC | 78 / 86 | UCI274C 120 kVA | SmartGen HGM6110N | 4.30 | ≤92 | 1050 kg 1950×900×1200 |
| KDGS90S | 113kVA/90.4 kW | 100kVA/80 kW | 144.3 | 4HTAA4.3-G34 SDEC | 95 / 105 | UCI274C 120 kVA | SmartGen HGM6110N | 4.30 | ≤92 | 1100 kg 1950×950×1200 |
| KDGS100S | 125kVA/100 kW | 112kVA/89.6 kW | 161.7 | 4HTAA4.3-G35 SDEC | 106 / 117 | UCI274D 135 kVA | SmartGen HGM6110N | 4.30 | ≤92 | 1110 kg 1950×950×1200 |
| 100–180 kW | ||||||||||
| KDGS120S | 150kVA/120 kW | 137kVA/109.6 kW | 197.7 | 4HTAA4.3-G36 SDEC | 120 / 132 | UCI274E 160 kVA | SmartGen HGM6110N | 4.30 | ≤92 | 1150 kg 1950×950×1200 |
| KDGS132S | 165kVA/132 kW | 150kVA/120 kW | 216.5 | 6HTAA6.5-G32 SDEC | 140 / 155 | UCI274G 180 kVA | SmartGen HGM6110N | 4.30 | ≤95 | 1360 kg 2350×950×1375 |
| KDGS150S | 187kVA/149.6 kW | 150kVA/120 kW | 216.5 | 6HTAA6.5-G35 SDEC | 155 / 170 | UCI274H 200 kVA | SmartGen HGM6110N | 4.30 | ≤95 | 1360 kg 2350×950×1375 |
| KDGS165S | 206kVA/164.8 kW | 187kVA/149.6 kW | 269.9 | 6HTAA6.5-G33 SDEC | 168 / 185 | UCI274J 230 kVA | SmartGen HGM6110N | 4.30 | ≤95 | 1410 kg 2320×950×1375 |
| KDGS180S | 225kVA/180 kW | 200kVA/160 kW | 288.7 | 6HTAA6.5-G34 SDEC | 186 / 205 | UCI274J 230 kVA | SmartGen HGM6110N | 4.30 | ≤95 | 1440 kg 2320×950×1375 |
| KDGS200S | 250kVA/200 kW | 225kVA/180 kW | 324.8 | 6DTAA8.9-G32 SDEC | 208 / 228 | UCD274K 250 kVA | SmartGen HGM6110N | 8.82 | ≤96 | 1830 kg 2550×1000×1385 |
| 200–320 kW | ||||||||||
| KDGS220S | 275kVA/220 kW | 250kVA/200 kW | 360.8 | 6DTAA8.9-G33 SDEC | 230 / 253 | HCI444D 300 kVA | SmartGen HGM6110N | 8.82 | ≤96 | 1950 kg 2550×1000×1470 |
| KDGS250S | 312kVA/249.6 kW | 275kVA/220 kW | 396.9 | 6DTAA8.9-G34 SDEC | 245 / 253 | HCI444ES 325 kVA | SmartGen HGM6110N | 8.82 | ≤96 | 1950 kg 2550×1000×1470 |
| KDGS280S | 350kVA/280 kW | 312kVA/249.6 kW | 450.3 | 6ETAA11.8-G32 SDEC | 280 / 308 | HCI444E 350 kVA | SmartGen HGM6110N | 11.82 | ≤97 | 2800 kg 3000×1250×1620 |
| KDGS300S | 375kVA/300 kW | 350kVA/280 kW | 505.2 | 6ETAA11.8-G33 SDEC | 307 / 338 | HCI444FS 380 kVA | SmartGen HGM6110N | 11.82 | ≤97 | 2550 kg 3100×1150×1620 |
| KDGS330S | 412kVA/329.6 kW | 375kVA/300 kW | 541.3 | 6ETAA11.8-G31 SDEC | 340 / 380 | HCI544C 500 kVA | SmartGen HGM6110N | 11.82 | ≤97 | 2800 kg 2950×1150×1620 |
| KDGS360S | 450kVA/360 kW | 400kVA/320 kW | 577.3 | 6ETAA12.8-G32 SDEC | 360 / 400 | HCI544C 500 kVA | SmartGen HGM6110N | 12.82 | ≤97 | 2700 kg 3100×1150×1620 |
| 350–500 kW | ||||||||||
| KDGS400S | 500kVA/400 kW | 450kVA/360 kW | 649.5 | 6ETAA12.8-G31 SDEC | 401 / 441 | HCI544C 500 kVA | SmartGen HGM6110N | 12.82 | ≤97 | 2700 kg 3300×1150×1620 |
| KDGS440S | 550kVA/440 kW | 500kVA/400 kW | 721.7 | 6ETAA12.8-G310 SDEC | 450 / 495 | HCI544D 550 kVA | SmartGen HGM6110N | 12.82 | ≤97 | 3100 kg 3100×1300×1770 |
| KDGS500S | 625kVA/500 kW | 562kVA/449.6 kW | 811.2 | 12GTAA27-G33 SDEC | 505 / 555 | HCI544FS 625 kVA | SmartGen HGM6110N | 26.60 | ≤103 | 4370 kg 3550×1690×2120 |
| KDGS550S | 687kVA/549.6 kW | 625kVA/500 kW | 902.1 | 12GTAA27-G32 SDEC | 565 / 622 | HCI634G 810 kVA | SmartGen HGM6110N | 26.60 | ≤103 | 4550 kg 3400×1690×2120 |
| 550–750 kW | ||||||||||
| KDGS620S | 750kVA/600 kW | 700kVA/560 kW | 1010.3 | 12GTAA27-G31 SDEC | 622 / 684 | HCI634G 810 kVA | SmartGen HGM6110N | 26.60 | ≤103 | 4550 kg 3400×1690×2120 |
| KDGS660S | 825kVA/660 kW | 750kVA/600 kW | 1082.5 | 6KTAA25-G32 SDEC | 685 / 754 | HCI634H 940 kVA | SmartGen HGM6110N | 25.20 | ≤112 | 5550 kg 3800×1640×2160 |
| KDGS720S | 900kVA/720 kW | 825kVA/660 kW | 1190.8 | 6KTAA25-G31 SDEC | 728 / 800 | HCI634H 940 kVA | SmartGen HGM6110N | 25.20 | ≤112 | 5650 kg 3900×1640×2160 |
| KDGS800S | 1000kVA/800 kW | 900kVA/720 kW | 1299 | 6KTAA25-G320 SDEC | 820 / 902 | S6L1D-C 1000 kVA | SmartGen HGM6110N | 25.20 | ≤112 | 6050 kg 4000×1750×2320 |
| 800–1000 kW | ||||||||||
| KDGS900S | 1125kVA/900 kW | 1000kVA/800 kW | 1443.3 | 6KTAA25-G321 SDEC | 880 / 968 | S6L1D-D 1125 kVA | SmartGen HGM6110N | 25.20 | ≤112 | 6250 kg 4000×1750×2320 |
| KDGS1000S | 1250kVA/1000 kW | 1125kVA/900 kW | 1623.8 | 6WTAA35-G310 SDEC | 1018 / 1120 | S6L1D-E 1250 kVA | SmartGen HGM6110N | 35.10 | ≤118 | 8000 kg 4500×2080×2450 |
| KDGS1100S | 1375kVA/1100 kW | 1250kVA/1000 kW | 1804.2 | 6WTAA35-G311 SDEC | 1118 / 1230 | S6L1D-F 1400 kVA | SmartGen HGM6110N | 35.10 | ≤118 | 8050 kg 4500×2080×2450 |
| 1100–1500 kW | ||||||||||
| KDGS1200S | 1500kVA/1200 kW | 1375kVA/1100 kW | 1984.6 | 12KTA58-G36 SDEC | 1280 / 1410 | S7L1D-C4 1550 kVA | SmartGen HGM6120N | 57.20 | ≤115 | 13550 kg 4500×2200×2515 |
| KDGS1350S | 1688kVA/1350.4 kW | 1563kVA/1250.4 kW | 2255.9 | 12KTA58-G35 SDEC | 1420 / 1560 | S7L1D-E4 1750 kVA | SmartGen HGM6120N | 57.20 | ≤115 | 13970 kg 4500×2200×2515 |
| KDGS1500S | 1875kVA/1500 kW | 1688kVA/1350.4 kW | 2436.3 | 12KTA58-G34 SDEC | 1560 / 1720 | S7L1D-F4 1900 kVA | SmartGen HGM6120N | 57.20 | ≤115 | 14430 kg 4600×2200×2515 |
| KDGS1650S | 2063kVA/1650.4 kW | 1875kVA/1500 kW | 2706.3 | 12KTA58-G33 SDEC | 1720 / 1890 | S7L1D-G4 2080 kVA | SmartGen HGM6120N | 57.20 | ≤115 | 14770 kg 4600×2200×2515 |
| ≥1600 kW | ||||||||||
| KDGS1800S | 2250kVA/1800 kW | 2000kVA/1600 kW | 2886.7 | 12KTA58-G32 SDEC | 1850 / 2035 | S7L1D-H4 2250 kVA | SmartGen HGM6120N | 57.20 | ≤115 | 15090 kg 4700×2200×2515 |
| KDGS2000S | 2500kVA/2000 kW | 2250kVA/1800 kW | 3247.5 | 12KTA58-G31 SDEC | 2010 / 2210 | S7L1D-J4 2500 kVA | SmartGen HGM6120N | 57.20 | ≤115 | 15260 kg 4700×2455×2515 |
| KDGS2200S | 2750kVA/2200 kW | 2500kVA/2000 kW | 3608.3 | 16KTA76-G33 SDEC | 2250 / 2500 | S7/P80/S9 series (factory-engineered) 2750 kVA | SmartGen HGM6120N | 76.30 | ≤122 | 18200 kg 6400×2560×2900 |
| KDGS2400S | 3000kVA/2400 kW | 2750kVA/2200 kW | 3969.2 | 16KTA76-G32 SDEC | 2510 / 2780 | S7/P80/S9 series (factory-engineered) 3000 kVA | SmartGen HGM6120N | 76.30 | ≤122 | 18500 kg 6400×2560×2900 |
| KDGS2600S | 3250kVA/2600 kW | 3000kVA/2400 kW | 4330 | 16KTA76-G31 SDEC | 2680 / 2950 | S7/P80/S9 series (factory-engineered) 3250 kVA | SmartGen HGM6120N | 76.30 | ≤122 | 18900 kg 6500×2830×2900 |
| KDGS2800S | 3500kVA/2800 kW | 3125kVA/2500 kW | 4510.4 | 16KTA76-G310 SDEC | 2773 / — | S7/P80/S9 series (factory-engineered) 3500 kVA | SmartGen HGM6120N | 76.30 | ≤122 | 19100 kg 6600×2830×3430 |
No model matches your filter. Try a shorter keyword or reset the filters.
Engines are sized with a power reserve over the alternator prime output (industry rule ≈ 1.05–1.22×). Every engine kW figure below is taken from the engine maker's published 1500 rpm / 50 Hz rating, not estimated.
Engine ratings: SDEC (Shanghai Diesel Engine) official catalogue. Alternator capacities: STAMFORD | AvK official ratings. Values for reference at ≤1000 m, ≤40 °C; final data follows the order contract.
SDEC (Shanghai Diesel Engine Co.) is the value option that most first-time importers overlook. The Z, D, E and G series cover 60–3000 kW at a lower cost per kW than Cummins or Perkins, with a parts pipeline that runs through Shanghai rather than through a Western distributor. For a rental fleet or a price-driven tender, SDEC is usually the winning bid.
SDEC engines are Chinese-designed and Chinese-built. They are not Cummins copies, but they are also not Cummins — the service interval is shorter and the fuel system is less tolerant of contamination. If your site has clean fuel and a competent mechanic, the cost saving is real.
The table above lists SDEC genset ratings from 60–3000 kW with the engine model, alternator frame and typical fuel consumption for each. Two columns decide most enquiries: the standby rating (what the set can carry for the duration of an outage) and the prime rating (what it can carry continuously). If you are comparing our table against another supplier's, check whether their figures are prime or standby — a standby rating quoted as prime is roughly 10 percent optimistic.
Jinjia Power is a diesel generator supplier and genset manufacturer in Dongguan, China, assembling every rating on this table in our own works and load-bank testing each unit at 100 percent rated output before shipment. Send the standby kVA you need, the voltage and frequency (50 or 60 Hz) and the destination port, and you get a firm quote inside one working day — engine model, alternator frame, controller, canopy grade and CIF price on one sheet. If the rating you need is not on the table, ask anyway: we build non-standard ratings as a normal option rather than a special order.
It lists 37 models from 66 kW to 2800 kW standby, with prime ratings from 60 kW to 2500 kW. SDEC is Shanghai Diesel, the value end of the Chinese engine market: simple, widely serviced and cheap to overhaul.
Standby is emergency duty with a varying load and no overload. Prime allows a 10 per cent overload for one hour in twelve and is the number to quote for continuous supply. Across this table standby averages about 1.10 times prime, so the same physical set carries two different numbers. Always state which one you are specifying against, because the price and the warranty follow the rating.
It is full-load line current at 400 V three phase, derived from the standby kVA: kVA times 1000 divided by root three times 400. Use it directly for cable and breaker sizing, then apply the derating for the ambient temperature and the installation method on site.
The engine carries the alternator losses as well as the electrical load. On this table the margin runs from about 1.05 to 1.22 times depending on the frame. An engine matched exactly to the alternator rating has nothing left for altitude, high ambient or a heavy direct-on-line motor start.
1000 m altitude or below and 40 degrees C ambient, taken from the engine maker's and the alternator maker's published catalogues. Above that the set derates by roughly 1 per cent per 100 m and 2 to 3 per cent per 5 degrees C. Send the site conditions with the enquiry and the quoted figure will be the derated one.
SmartGen HGM420N on the smaller frames and HGM6110N or HGM6120N from roughly 100 kW upward. The controller is a specification item, not fixed — Deep Sea, ComAp or a specific paralleling panel can be built instead if the project standard names one.
Price and parts access. An SDEC set typically lands 20 to 35 per cent below the equivalent Perkins or Volvo build, and the engine is simple enough that a workshop with basic diesel experience can service it. The trade-off is shorter overhaul intervals and a narrower dealer network outside Asia. For a rental fleet or a project where the client names no brand, it is usually the commercial answer.
The 4- and 6-cylinder D series at the bottom and the larger 6D and 12V frames up to 2500 kW prime. All are water-cooled, four-stroke, and all are genuine SDEC rather than a licensed copy, so parts come through the SDEC channel.
Yes. The table is the commonly built range. Different voltages, 60 Hz builds, marine duty engines, silent canopies, container packages and dual-bearing alternators are all normal variations. Give the duty, the site conditions and the voltage and the closest frame is quoted with the deviation listed.
Standard frames ship in 3 to 7 working days from the factory for a single set, longer for a containerised or paralleling package. There is no minimum order for a single genset. Sets leave from Shenzhen or Guangzhou port, and the export terms are normally 30 per cent deposit with the balance before shipment.