Home › Mitsubishi Generators › Technical Selection Table

Mitsubishi Heavy Industries Powered Generator Sets

Mitsubishi Genset Technical Selection Table — S6R / S12R / S16R Series

Each model lists the complete power chain: genset model standby / prime (kVA & kW) rated current genuine Mitsubishi MHI engine with prime/standby kW Stamford alternator with kVA controller. Built on the Mitsubishi S-series heavy-duty industrial engines.

13standard models 400–1800 kWprime range 50 Hz / 1500 rpm400/230 V, PF 0.8 Mitsubishi MHI + Stamfordgenuine brands
Genset Model Genset Output @ 50 Hz Engine Alternator (Stamford) Controller
StandbykVA / kW (ESP) PrimekVA / kW (PRP) CurrentA @ 400 V Engine Model Eng. P/Sprime / standby kW
350–500 kW
JJSL-480GF660kVA/528 kW600kVA/480 kW866
S6R-PTA
Mitsubishi
515 / 570
HCI544F
670 kVA
SmartGen HGM6110N
JJSL-520GF715kVA/572 kW650kVA/520 kW938.2
S6R2-PTA
Mitsubishi
595 / 655
HCI634G
810 kVA
SmartGen HGM6110N
550–750 kW
JJSL-600GF825kVA/660 kW750kVA/600 kW1082.5
S6R2-PTAA
Mitsubishi
665 / 730
HCI634H
940 kVA
SmartGen HGM6110N
800–1000 kW
JJSL-800GF1100kVA/880 kW1000kVA/800 kW1443.3
S12H-PTA
Mitsubishi
930 / 1020
S6L1D-D
1125 kVA
SmartGen HGM6110N
JJSL-800GF1100kVA/880 kW1000kVA/800 kW1443.3
S12H-PTA
Mitsubishi
930 / 1020
S6L1D-D
1125 kVA
SmartGen HGM6110N
JJSL-1000GF1375kVA/1100 kW1250kVA/1000 kW1804.2
S12R-PTA
Mitsubishi
1110 / 1220
S6L1D-F
1400 kVA
SmartGen HGM6110N
1100–1500 kW
JJSL-1100GF1512kVA/1209.6 kW1375kVA/1100 kW1984.6
S12R-PTA2
Mitsubishi
1195 / 1315
S7L1D-C4
1550 kVA
SmartGen HGM6120N
JJSL-1200GF1650kVA/1320 kW1500kVA/1200 kW2165
S12R-PTAA2
Mitsubishi
1314 / 1441
S7L1D-D4
1650 kVA
SmartGen HGM6120N
JJSL-1200GF1650kVA/1320 kW1500kVA/1200 kW2165
S12R-PTAA2
Mitsubishi
1314 / 1441
S7L1D-D4
1650 kVA
SmartGen HGM6120N
JJSL-1300GF1788kVA/1430.4 kW1625kVA/1300 kW2345.4
S16R-PTA
Mitsubishi
1480 / 1620
S7L1D-F4
1900 kVA
SmartGen HGM6120N
JJSL-1500GF2062kVA/1649.6 kW1875kVA/1500 kW2706.3
S16R-PTA2
Mitsubishi
1630 / 1790
S7L1D-G4
2080 kVA
SmartGen HGM6120N
≥1600 kW
JJSL-1600GF2200kVA/1760 kW2000kVA/1600 kW2886.7
S16R-PTAA2
Mitsubishi
1728 / 1939
S7L1D-H4
2250 kVA
SmartGen HGM6120N
JJSL-1800GF2475kVA/1980 kW2250kVA/1800 kW3247.5
S16R2-PTAW
Mitsubishi
1960 / 2167
S7L1D-J4
2500 kVA
SmartGen HGM6120N

No model matches your filter. Try a shorter keyword or reset the filters.

Power definitions (ISO 8528)

  • PRP (Prime) — unlimited-hours base power; 10% overload for 1 h in every 12 h.
  • ESP (Standby) — emergency maximum, no overload (typically +10% over prime).
  • Rated current I = Prime kW / (√3 × 400 V), three-phase PF 0.8.

Engine-to-set matching

Engines are sized with a power reserve over the alternator prime output (industry rule ≈ 1.05–1.22×). Every engine kW figure below is taken from the engine maker's published 1500 rpm / 50 Hz rating, not estimated.

Configuration & options

  • Alternator: genuine Stamford, brushless, H-class, IP23, PF 0.8.
  • Controller: SmartGen HGM series standard; Deep Sea DSE6120/7320 on request.
  • Open / silent / super-silent / trailer types; ATS, parallel & remote-monitoring optional.

Data sources

Engine ratings: Mitsubishi Heavy Industries engine technical data. Alternator capacities: STAMFORD | AvK official ratings. Values for reference at ≤1000 m, ≤40 °C; final data follows the order contract.

Need a quoted datasheet or custom configuration?
Tell us the required kW, standby/base use and sound level — we reply with factory price & specs.