Mitsubishi Heavy Industries Powered Generator Sets
Each model lists the complete power chain: genset model standby / prime (kVA & kW) rated current genuine Mitsubishi MHI engine with prime/standby kW Stamford alternator with kVA controller. Built on the Mitsubishi S-series heavy-duty industrial engines.
| Genset Model | Genset Output @ 50 Hz | Engine | Alternator (Stamford) | Controller | |||
|---|---|---|---|---|---|---|---|
| StandbykVA / kW (ESP) | PrimekVA / kW (PRP) | CurrentA @ 400 V | Engine Model | Eng. P/Sprime / standby kW | |||
| 350–500 kW | |||||||
| JJSL-480GF | 660kVA/528 kW | 600kVA/480 kW | 866 | S6R-PTA Mitsubishi | 515 / 570 | HCI544F 670 kVA | SmartGen HGM6110N |
| JJSL-520GF | 715kVA/572 kW | 650kVA/520 kW | 938.2 | S6R2-PTA Mitsubishi | 595 / 655 | HCI634G 810 kVA | SmartGen HGM6110N |
| 550–750 kW | |||||||
| JJSL-600GF | 825kVA/660 kW | 750kVA/600 kW | 1082.5 | S6R2-PTAA Mitsubishi | 665 / 730 | HCI634H 940 kVA | SmartGen HGM6110N |
| 800–1000 kW | |||||||
| JJSL-800GF | 1100kVA/880 kW | 1000kVA/800 kW | 1443.3 | S12H-PTA Mitsubishi | 930 / 1020 | S6L1D-D 1125 kVA | SmartGen HGM6110N |
| JJSL-800GF | 1100kVA/880 kW | 1000kVA/800 kW | 1443.3 | S12H-PTA Mitsubishi | 930 / 1020 | S6L1D-D 1125 kVA | SmartGen HGM6110N |
| JJSL-1000GF | 1375kVA/1100 kW | 1250kVA/1000 kW | 1804.2 | S12R-PTA Mitsubishi | 1110 / 1220 | S6L1D-F 1400 kVA | SmartGen HGM6110N |
| 1100–1500 kW | |||||||
| JJSL-1100GF | 1512kVA/1209.6 kW | 1375kVA/1100 kW | 1984.6 | S12R-PTA2 Mitsubishi | 1195 / 1315 | S7L1D-C4 1550 kVA | SmartGen HGM6120N |
| JJSL-1200GF | 1650kVA/1320 kW | 1500kVA/1200 kW | 2165 | S12R-PTAA2 Mitsubishi | 1314 / 1441 | S7L1D-D4 1650 kVA | SmartGen HGM6120N |
| JJSL-1200GF | 1650kVA/1320 kW | 1500kVA/1200 kW | 2165 | S12R-PTAA2 Mitsubishi | 1314 / 1441 | S7L1D-D4 1650 kVA | SmartGen HGM6120N |
| JJSL-1300GF | 1788kVA/1430.4 kW | 1625kVA/1300 kW | 2345.4 | S16R-PTA Mitsubishi | 1480 / 1620 | S7L1D-F4 1900 kVA | SmartGen HGM6120N |
| JJSL-1500GF | 2062kVA/1649.6 kW | 1875kVA/1500 kW | 2706.3 | S16R-PTA2 Mitsubishi | 1630 / 1790 | S7L1D-G4 2080 kVA | SmartGen HGM6120N |
| ≥1600 kW | |||||||
| JJSL-1600GF | 2200kVA/1760 kW | 2000kVA/1600 kW | 2886.7 | S16R-PTAA2 Mitsubishi | 1728 / 1939 | S7L1D-H4 2250 kVA | SmartGen HGM6120N |
| JJSL-1800GF | 2475kVA/1980 kW | 2250kVA/1800 kW | 3247.5 | S16R2-PTAW Mitsubishi | 1960 / 2167 | S7L1D-J4 2500 kVA | SmartGen HGM6120N |
No model matches your filter. Try a shorter keyword or reset the filters.
Engines are sized with a power reserve over the alternator prime output (industry rule ≈ 1.05–1.22×). Every engine kW figure below is taken from the engine maker's published 1500 rpm / 50 Hz rating, not estimated.
Engine ratings: Mitsubishi Heavy Industries engine technical data. Alternator capacities: STAMFORD | AvK official ratings. Values for reference at ≤1000 m, ≤40 °C; final data follows the order contract.