50–625 kVA Prime | 55–688 kVA Standby | Diesel Generator Sets Quoted in kVA
Prime and standby ratings for every set we build — both figures shown, because the number on the nameplate is not always the number you can run.
| Prime kVA (PRP) | Prime kW | Standby kVA (ESP) | Standby kW | Model |
|---|---|---|---|---|
| 50 kVA | 40 kW | 55 kVA | 44 kW | JJP-M40GF |
| 75 kVA | 60 kW | 83 kVA | 66 kW | JJP-M60GF |
| 100 kVA | 80 kW | 110 kVA | 88 kW | JJP-M80GF |
| 125 kVA | 100 kW | 138 kVA | 110 kW | JJP-M100GF |
| 187 kVA | 150 kW | 206 kVA | 165 kW | JJP-M150GF |
| 250 kVA | 200 kW | 275 kVA | 220 kW | JJP-M200GF |
| 312 kVA | 250 kW | 344 kVA | 275 kW | JJP-M250GF |
| 375 kVA | 300 kW | 413 kVA | 330 kW | JJP-M300GF |
| 437 kVA | 350 kW | 481 kVA | 385 kW | JJP-M350GF |
| 500 kVA | 400 kW | 550 kVA | 440 kW | JJP-M400GF |
| 562 kVA | 450 kW | 619 kVA | 495 kW | JJP-M450GF |
| 625 kVA | 500 kW | 688 kVA | 550 kW | JJP-M500GF |
Sizing by kVA? Detailed pages: 100 kVA generator · 200 kVA generator · 250 kVA generator · 375 kVA generator · 500 kVA generator — amps per phase, dimensions, weight, fuel consumption and price for each size.
Ratings at 0.8 power factor, 400/230 V, 50 Hz. 60 Hz builds and other voltages quoted on request. Larger sets up to 3000 kW available — send us the kVA you need.
A kVA generator is rated in apparent power; a kW rating is real power. The gap between them is the power factor, and for a standard diesel genset that factor is 0.8. So a set sold as 100 kVA delivers 80 kW to the load — the other 20 kVA is reactive power the alternator has to carry but the load never converts into work.
This matters because the two numbers are not interchangeable in a quotation. If you ask for a 100 kVA generator and the supplier ships a 100 kW set, you have bought 125 kVA — roughly 25 percent more machine than you asked for, and you paid for it. If they ship a 80 kW set labelled as 100 kVA, you got what you asked for. Ask which figure is on the nameplate before you compare prices.
Motor loads, transformers and UPS systems all pull current that does not convert to useful work, which is why the kVA figure — not the kW figure — is what actually sizes the alternator and the breaker.
The numbers buyers ask for most, plus the next size up in each direction.
| Rating | Real power at 0.8 PF | Same kW, expressed in kVA | Same kVA, expressed in kW |
|---|---|---|---|
| 50 kVA | 40 kW | 62 kVA | 50 kVA |
| 75 kVA | 60 kW | 94 kVA | 75 kVA |
| 100 kVA | 80 kW | 125 kVA | 100 kVA |
| 125 kVA | 100 kW | 156 kVA | 125 kVA |
| 150 kVA | 120 kW | 188 kVA | 150 kVA |
| 187 kVA | 150 kW | 234 kVA | 188 kVA |
| 200 kVA | 160 kW | 250 kVA | 200 kVA |
| 250 kVA | 200 kW | 312 kVA | 250 kVA |
| 312 kVA | 250 kW | 390 kVA | 312 kVA |
| 375 kVA | 300 kW | 469 kVA | 375 kVA |
| 437 kVA | 350 kW | 546 kVA | 438 kVA |
| 500 kVA | 400 kW | 625 kVA | 500 kVA |
| 562 kVA | 450 kW | 702 kVA | 562 kVA |
| 625 kVA | 500 kW | 781 kVA | 625 kVA |
| 688 kVA | 550 kW | 860 kVA | 688 kVA |
If you are sourcing from the UAE, Saudi Arabia, Nigeria, Ghana, Kenya, South Africa, the UK, Malaysia or Singapore, your tender documents and your consultant's load schedule will almost certainly be written in kVA. That is not a translation problem — it is the standard. IEC and BS practice sizes the alternator in apparent power, and the kVA figure is what appears on the datasheet, the type test certificate and the shipping documents.
Buyers in North America work the other way round, in kW and in amperes at 480 V. If you send a US-specification enquiry to a supplier who quotes in kVA, or the reverse, the two quotes will look 20 percent apart when they are describing the same machine. We quote both figures on every datasheet so the comparison is unambiguous.
kVA ratings at 50 Hz, 400/230 V. Ambient above 40°C derates the set — tell us the site temperature and the rating we quote will be the one that holds at that temperature, not the catalogue figure measured at 25°C.
kVA is the working unit across West and East Africa, and Perkins-powered sets carry a strong resale and parts reputation in this region. We supply Perkins, Cummins and Weichai options in the same kVA frame.
kVA plus a noise figure. Where a sound level is specified in the enquiry — 65 dBA at 7 m is common — a silenced canopy is a line item, not an upgrade nobody quoted.
Sizing starts from the load list, not from a rule of thumb. Three figures decide the rating:
Send us the load list and the duty and we will tell you which kVA rating covers it, including the surge case. Where the answer lands between two catalogue sizes, we say so rather than quoting the larger one to be safe.
Related reading: diesel generator sets · silent generators · industrial generators · containerised generators · full catalogue
kVA is apparent power — the total current the alternator and cables must carry. kW is real power — the part that does useful work. On a standard diesel genset the power factor is 0.8, so kW = kVA × 0.8. A 100 kVA generator delivers 80 kW.
Multiply kVA by the power factor. At the standard 0.8 PF, 50 kVA = 40 kW, 100 kVA = 80 kW, 250 kVA = 200 kW, 500 kVA = 400 kW. To go the other way, divide kW by 0.8: 200 kW = 250 kVA.
IEC and BS practice rates the alternator in apparent power, so tenders, load schedules and type test certificates across the Middle East, Africa, the UK and most of Asia are written in kVA. North America works in kW. Both describe the same machine — the conversion is 0.8 power factor.
Add up the running kVA of every load that operates simultaneously, then check the starting kVA of the largest motor — usually 5 to 7 times its running current. The set must cover both. Send us the load list and we will size it, including the surge case.
Yes. Our standard range runs from 50 kVA to 625 kVA prime (55 to 688 kVA standby), in 12 frame sizes, with Cummins, Perkins, Volvo, Weichai, Yuchai, SDEC and Yangdong engine options. Larger sets up to 3000 kW are built to order.
Prime (PRP) is for continuous operation with a 10 percent overload for one hour in twelve. Standby (ESP) is for mains failure only, limited to around 200 hours a year, and is typically 10 percent higher than prime. Running a standby-rated set as prime shortens its life — the derating is real.
Yes. Standard build is 50 Hz, 400/230 V. We also build 60 Hz at 480/277 V, 440/254 V, 380/220 V and other site voltages. Tell us the frequency and voltage in the enquiry and the kVA rating stays the same — only the alternator winding changes.
Load list, duty cycle, site temperature, frequency and voltage — send those five things and you get a datasheet, not a brochure.