1000 kVA diesel generator set

1000 kVA GENERATOR

JJP-M800GF — 1000 kVA / 800 kW prime, 1100 kVA / 880 kW standby. 1,443 A per phase at 400 V, 179.1 L/h at full load. FOB China quoted against the engine and alternator you specify.

See the Full Specification
Other ratings in this range 100 kVA150 kVA200 kVA250 kVA300 kVA375 kVA400 kVA500 kVA625 kVA800 kVA1000 kVA1500 kVAAll 50–1500 kVA

1000 kVA Generator — JJP-M800GF

Prime (PRP)
1000 kVA
800 kW at 0.8 PF
Unlimited hours, 10% overload for 1 h in 12
Standby (ESP)
1100 kVA
880 kW at 0.8 PF
Loss of mains only, 200 h/yr

1000 kVA is the prime rating on the nameplate, not a rounded-up figure — the frame maps exactly onto the requirement. 1500 rpm at 50 Hz, 1800 rpm at 60 Hz, three-phase four-wire, 0.8 power factor.

How Many Amps Is a 1000 kVA Generator?

VoltagePhaseCurrent at 1000 kVASuggested breaker frame
380 V3-phase1,519 A2,000 A
400 V3-phase1,443 A2,000 A
415 V3-phase1,391 A2,000 A
440 V3-phase1,312 A2,000 A
480 V3-phase1,203 A1,600 A
220 V1-phase4,545 Aspecial winding
240 V1-phase4,167 Aspecial winding

I = kVA × 1000 ÷ (√3 × V). Breaker sizing at 125% of the 400 V figure gives 1,804 A, which lands on a 2,500 A frame. At this current the run is busbar or 5 × 150 mm² copper per phase rather than a single cable; the switchboard is normally a bespoke panel, not a moulded case breaker.

Fuel Consumption per Hour

LoadDiesel L/hUS gal/h
1000 kVA / 800 kW (100%)179.1 L/h47.3
800 kVA / 640 kW (80%)143.3 L/h37.9
600 kVA / 480 kW (60%)107.5 L/h28.4
400 kVA / 320 kW (40%)71.6 L/h18.9
200 kVA / 160 kW (20%)35.8 L/h9.5

Based on ≤187 g/kWh at 835 g/L diesel density — the same basis used across this site, so the figures compare directly with our other ratings. Consumption tracks load almost linearly in this class. The exact curve for the engine finally fitted is issued with the test report.

Engine and Alternator on the 1000 kVA Frame

BrandEngine modelRatingStandby outputCylinders
YuchaiYC6C1320-D311320 PS971 kW6-cyl

Coupled to a Faraday FD6C-4 alternator, with a Deep Sea DSE7320 MKII controller as standard and DSE8610 for parallel operation. The Yuchai figure above is the engine rating; it clears the 800 kW prime requirement with margin, which is the match we apply across the range (engine sized at 1.1–1.15× the alternator output). Weichai, Cummins, Perkins and Volvo equivalents in the same power band are available on request — tell us the brand your service network already stocks and we will confirm the model and the price against it.

What Can a 1000 kVA Generator Power?

Data centre or colocation campus
70–90 racks at 10 kW each. The generator bus normally carries UPS, cooling and the fire pump together, and parallel operation is standard.
Industrial park or heavy process
640–720 kW of connected load. Confirm the largest motor and the permitted voltage dip before fixing the frame.
Steel, cement or chemical plant
Process drives and auxiliaries on a standby bus. High-harmonic loads need the alternator derated — state the load type when enquiring.
Hospital campus or teaching hospital
600–700 beds. Zone the bus so the generator carries clinical circuits, theatres and the cold chain first.
Large desalination or irrigation scheme
High-voltage pump motors on soft start. Sequence the starts; the set will not carry two large pumps starting together.
Airport, port or rail depot
Terminal and handling equipment on standby, with the set running for extended periods during grid outages.

Frame, Weight and Installation

Overall dimensions and dry weight move with the engine and the alternator actually fitted, so we do not publish a single figure for this rating and then quote you a set that does not match it. The general arrangement drawing issued with your order carries the exact envelope, lifting points and centre of gravity for the configuration you buy.

What does not change is the site work. Allow clearance at the alternator end for cooling air, confirm canopy door swing on both long sides before siting, and cast a level concrete plinth rated for 1.5× the wet weight. At this rating the set is a crane lift and normally arrives as a containerised or skid-mounted unit. Confirm the lifting plan and the floor loading with the GA drawing in hand.

Ask for the drawing for the engine you are considering — it is the only number worth designing a plant room around.

What Does a 1000 kVA Generator Cost?

At this rating the engine and the alternator together account for most of the cost, and the band between a cost-competitive build and a premium build is wider than at the smaller frames. We quote this rating against the engine and alternator you specify rather than publishing a catalogue band. What we need to give you a firm number: running kW and the largest motor, the duty (standby, prime or continuous), the destination port, and whether you want open skid, silent canopy or container. From those we confirm the engine option, the tank size and the canopy grade, and price it landed-ready. A sound-attenuated canopy typically adds 8–12% and roughly 200–300 kg at this rating; a synchronising panel, an ATS and the breaker are priced separately because they depend on the switchboard you already have.

1000 kVA Generator Questions

How many amps does a 1000 kVA generator deliver?

1,443 A per phase at 400 V three-phase, 1,519 A at 380 V, 1,203 A at 480 V. Size the breaker at 125% of the 400 V figure: that gives 1,804 A, which lands on a 2,500 A frame.

What does a 1000 kVA generator weigh?

Weight depends on the engine and alternator fitted, so we do not publish a single figure for this rating. The general arrangement drawing issued with your order carries the exact dry weight, the lifting points and the centre of gravity for the configuration you buy — ask for it for the engine you are considering before you design the plant room.

How much fuel does a 1000 kVA generator use per hour?

About 179.1 L/h at full 800 kW load and 89.6 L/h at half load, on the ≤187 g/kWh basis used across this site. Consumption is close to linear with load in this class, so the fuel bill per kWh barely moves between 50% and 100% load.

Is 1000 kVA the same as 800 kW?

At 0.8 power factor, yes — 1000 × 0.8 = 800 kW. A lower site power factor reduces the usable kW further, so check the PF before confirming the rating.

What is the standby rating of this set?

1100 kVA / 880 kW, which is 10% above prime. Standby is for loss of mains only and is rated at 200 hours a year; if the set runs as the main supply, specify it at prime instead.

Can two 1000 kVA sets run in parallel?

Yes, with the DSE8610 controller, matching alternator pitch and a synchronising panel. Two sets give 2000 kVA total, or N+1 redundancy at 1000 kVA. Specify it at the quote stage — retro-fitting is expensive.

Which engine brand should I choose?

The Yuchai YC6C1320-D31 is the configuration in our standard quotation for this rating. Weichai, Cummins, Perkins and Volvo equivalents in the same power band are available on request. Choose on parts availability where you operate: Cummins and Perkins have the widest network across Africa and the Middle East, Weichai and Yuchai are the cost-competitive options with strong regional support, Volvo suits projects with emission or brand requirements.

What noise level should I expect?

65–75 dB(A) at 7 m for a canopied set, depending on acoustic grade. Residential-grade units sit at the low end; standard export canopies at the high end. Open skid sets are not normally specified where noise matters.

Send the load schedule, get a firm FOB price