400 kVA diesel generator set

400 kVA GENERATOR

JJP-M320GF — 400 kVA / 320 kW prime, 440 kVA / 352 kW standby. 577 A per phase at 400 V, 71.6 L/h at full load. FOB China quoted against the engine and alternator you specify.

See the Full Specification
Other ratings in this range 100 kVA150 kVA200 kVA250 kVA300 kVA375 kVA400 kVA500 kVA625 kVA800 kVA1000 kVA1500 kVAAll 50–1500 kVA

400 kVA Generator — JJP-M320GF

Prime (PRP)
400 kVA
320 kW at 0.8 PF
Unlimited hours, 10% overload for 1 h in 12
Standby (ESP)
440 kVA
352 kW at 0.8 PF
Loss of mains only, 200 h/yr

400 kVA is the prime rating on the nameplate, not a rounded-up figure — the frame maps exactly onto the requirement. 1500 rpm at 50 Hz, 1800 rpm at 60 Hz, three-phase four-wire, 0.8 power factor.

How Many Amps Is a 400 kVA Generator?

VoltagePhaseCurrent at 400 kVASuggested breaker frame
380 V3-phase608 A800 A
400 V3-phase577 A800 A
415 V3-phase556 A800 A
440 V3-phase525 A800 A
480 V3-phase481 A630 A
220 V1-phase1,818 Aspecial winding
240 V1-phase1,667 Aspecial winding

I = kVA × 1000 ÷ (√3 × V). Breaker sizing at 125% of the 400 V figure gives 722 A, which lands on a 1,000 A frame. Cable at the 400 V figure needs roughly 2 × 120 mm² copper per phase for a run under 50 m.

Fuel Consumption per Hour

LoadDiesel L/hUS gal/h
400 kVA / 320 kW (100%)71.6 L/h18.9
320 kVA / 256 kW (80%)57.3 L/h15.1
240 kVA / 192 kW (60%)43.0 L/h11.4
160 kVA / 128 kW (40%)28.7 L/h7.6
80 kVA / 64 kW (20%)14.3 L/h3.8

Based on ≤187 g/kWh at 835 g/L diesel density — the same basis used across this site, so the figures compare directly with our other ratings. Consumption tracks load almost linearly in this class. The exact curve for the engine finally fitted is issued with the test report.

Engine and Alternator on the 400 kVA Frame

BrandEngine modelRatingStandby outputCylinders
YuchaiYC6MJ540-D30540 PS397 kW6-cyl

Coupled to a Faraday FD4LP-4 alternator, with a Deep Sea DSE7320 MKII controller as standard and DSE8610 for parallel operation. The Yuchai figure above is the engine rating; it clears the 320 kW prime requirement with margin, which is the match we apply across the range (engine sized at 1.1–1.15× the alternator output). Weichai, Cummins, Perkins and Volvo equivalents in the same power band are available on request — tell us the brand your service network already stocks and we will confirm the model and the price against it.

What Can a 400 kVA Generator Power?

Heavy factory or process plant
255–290 kW of connected load. At this size the constraint is usually the largest single motor, not the total — check the locked-rotor kVA before confirming.
Regional hospital
180–260 beds including theatres, imaging and a cold chain. Commonly 2 × 400 kVA in parallel for N+1.
Data hall
22–30 racks at 10 kW each, with UPS, cooling and the fire pump on the generator bus.
Commercial complex
8,000–10,000 m² of mixed retail and office. Chiller starting is the design case — soft-start or VSD chillers let a smaller frame carry the same building.
Mining camp or crushing circuit
Crusher, conveyors, workshop and accommodation block. Heavy-duty filtration and a fuel polishing loop are normal specification here.
Municipal water or wastewater plant
Blowers and large pumps on a sequenced start. Specify the start sequence at the design stage, not after commissioning.

Frame, Weight and Installation

Overall dimensions and dry weight move with the engine and the alternator actually fitted, so we do not publish a single figure for this rating and then quote you a set that does not match it. The general arrangement drawing issued with your order carries the exact envelope, lifting points and centre of gravity for the configuration you buy.

What does not change is the site work. Allow clearance at the alternator end for cooling air, confirm canopy door swing on both long sides before siting, and cast a level concrete plinth rated for 1.5× the wet weight. At this rating a canopied set is a crane lift. Plan the access route before the plant room doors go in.

Ask for the drawing for the engine you are considering — it is the only number worth designing a plant room around.

What Does a 400 kVA Generator Cost?

At this rating the same frame spans a wide band between a Yuchai or Weichai build and a Cummins or Perkins build, so a single published figure would be misleading. We quote this rating against the engine and alternator you specify rather than publishing a catalogue band. What we need to give you a firm number: running kW and the largest motor, the duty (standby, prime or continuous), the destination port, and whether you want open skid, silent canopy or container. From those we confirm the engine option, the tank size and the canopy grade, and price it landed-ready. A sound-attenuated canopy typically adds 8–12% and roughly 200–300 kg at this rating; a synchronising panel, an ATS and the breaker are priced separately because they depend on the switchboard you already have.

400 kVA Generator Questions

How many amps does a 400 kVA generator deliver?

577 A per phase at 400 V three-phase, 608 A at 380 V, 481 A at 480 V. Size the breaker at 125% of the 400 V figure: that gives 722 A, which lands on a 1,000 A frame.

What does a 400 kVA generator weigh?

Weight depends on the engine and alternator fitted, so we do not publish a single figure for this rating. The general arrangement drawing issued with your order carries the exact dry weight, the lifting points and the centre of gravity for the configuration you buy — ask for it for the engine you are considering before you design the plant room.

How much fuel does a 400 kVA generator use per hour?

About 71.6 L/h at full 320 kW load and 35.8 L/h at half load, on the ≤187 g/kWh basis used across this site. Consumption is close to linear with load in this class, so the fuel bill per kWh barely moves between 50% and 100% load.

Is 400 kVA the same as 320 kW?

At 0.8 power factor, yes — 400 × 0.8 = 320 kW. A lower site power factor reduces the usable kW further, so check the PF before confirming the rating.

What is the standby rating of this set?

440 kVA / 352 kW, which is 10% above prime. Standby is for loss of mains only and is rated at 200 hours a year; if the set runs as the main supply, specify it at prime instead.

Can two 400 kVA sets run in parallel?

Yes, with the DSE8610 controller, matching alternator pitch and a synchronising panel. Two sets give 800 kVA total, or N+1 redundancy at 400 kVA. Specify it at the quote stage — retro-fitting is expensive.

Which engine brand should I choose?

The Yuchai YC6MJ540-D30 is the configuration in our standard quotation for this rating. Weichai, Cummins, Perkins and Volvo equivalents in the same power band are available on request. Choose on parts availability where you operate: Cummins and Perkins have the widest network across Africa and the Middle East, Weichai and Yuchai are the cost-competitive options with strong regional support, Volvo suits projects with emission or brand requirements.

What noise level should I expect?

65–75 dB(A) at 7 m for a canopied set, depending on acoustic grade. Residential-grade units sit at the low end; standard export canopies at the high end. Open skid sets are not normally specified where noise matters.