SAME DAY SHIPPING ON ALL STOCKED PRODUCTS
86-0769-89610677 / 86-13553838770 | info@jinjiadongli.com
150 kVA diesel generator set

150 kVA GENERATOR

150 kVA / 120 kW prime, 165 kVA / 132 kW standby. 217 A per phase at 400 V, 27.6 L/h at full load. Built to order on the M120 frame — engine and alternator specified to your load list.

See the Full Specification
Other ratings in this range 100 kVA 150 kVA 200 kVA 250 kVA 375 kVA 500 kVA 625 kVA All 50–625 kVA

150 kVA Generator — 120 kW Prime

Prime (PRP)
150 kVA
120 kW at 0.8 PF
Unlimited hours, 10% overload for 1 h in 12
Standby (ESP)
165 kVA
132 kW at 0.8 PF
Loss of mains only, 200 h/yr

150 kVA is the prime rating on the nameplate, not a rounded-up figure. 1500 rpm at 50 Hz, 1800 rpm at 60 Hz, three-phase four-wire, 0.8 power factor. The frame is built to order, so the engine and alternator are matched to the load list at quotation rather than pulled from a fixed catalogue combination.

How Many Amps Is a 150 kVA Generator?

VoltagePhaseCurrent at 150 kVASuggested breaker frame
380 V3-phase228 A320 A
400 V3-phase217 A320 A
415 V3-phase209 A320 A
440 V3-phase197 A250 A
480 V3-phase180 A250 A
220 V1-phase682 Aspecial winding
240 V1-phase625 Aspecial winding

I = kVA × 1000 ÷ (√3 × V). Breaker sizing at 125% of the 400 V figure gives 271 A, so a 320 A frame. Cable at 217 A needs roughly 2 × 70 mm² copper per phase for a run under 50 m, or 1 × 120 mm² where the run is short and derating allows. A single-phase 150 kVA set needs a bespoke alternator — balance the load across three phases instead.

Fitting a 150 kVA Set into the Plant Room

This rating is assembled to order, so the drawing package is issued with the quotation rather than published here — overall length, width and weight depend on the engine you choose and whether the set carries a canopy or an open skid. What does not change is the siting logic, and that is where most installs go wrong.

ItemWhat to allow
Access at the alternator end1 m clear for cooling air intake and for pulling the alternator if it ever needs rewinding
Radiator end1.5 m clear, and the hot air must not recirculate back into the intake — duct it out of the room
Side clearanceCanopy doors swing on both long sides; leave the door width plus 300 mm
PlinthLevel concrete rated for 1.5× the wet weight of the set plus tank
Door and lift routeConfirm the canopy fits through the plant room door before it ships — this is the most expensive mistake to fix later
ExhaustRouted to open air with a flexible section; do not let the silencer carry the weight of the pipe run

Send us the plant room dimensions and the door opening and we will confirm the layout on the GA drawing before the order is released.

Fuel Consumption per Hour

LoadDiesel L/hUS gal/h
150 kVA / 120 kW (100%)27.6 L/h7.3
120 kVA / 96 kW (80%)22.1 L/h5.8
90 kVA / 72 kW (60%)16.6 L/h4.4
60 kVA / 48 kW (40%)11.0 L/h2.9
30 kVA / 24 kW (20%)5.5 L/h1.5

About 0.184 L per kVA per hour at rated load. Consumption tracks load almost linearly in this class, so a set held at 50% for 12 hours a day burns roughly half the full-load figure for twice as long: the fuel bill per kWh barely changes, but the engine runs cleaner and the service interval stretches.

Fuel Tank Capacity and Runtime

Runtime is tank volume divided by consumption at the load you actually run. The baseframe tank is built to the order, so start from the runtime you need and work back to the volume.

Baseframe tankRuntime at full load (27.6 L/h)Runtime at 50% load (13.8 L/h)
300 L10.9 h21.7 h
400 L14.5 h29.0 h
500 L18.1 h36.2 h
600 L21.7 h43.5 h
800 L (silent canopy)29.0 h58.0 h

Engine Selection at 120 kW Prime

The 150 kVA frame is built to order, so the engine is a specification decision rather than a fixed model number. Four brands cover almost every enquiry at this rating, and the choice moves price, parts availability and serviceability more than any other line on the quote.

BrandChoose it whenWatch out for
WeichaiCost matters and the site is in Asia, Africa or the Middle East where parts are stockedConfirm the standby rating clears the load with margin before releasing
CumminsParts network and resale value drive the decision, or the tender names the brandHighest price in the band
PerkinsSimilar to Cummins on availability, often keener on price in Europe-facing projectsCheck the specific fuel curve at part load if fuel cost is the deciding factor
VolvoEmissions or brand specification is written into the contractLead time and price premium

Alternators are matched to the engine at the same time — Stamford, Leroy Somer or a comparable Chinese build — and the whole set is load-bank tested at rated output before it leaves the floor. Tell us the destination country and the duty and we will propose the engine rather than leaving you to pick a name.

What Can a 150 kVA Generator Power?

Small hotel or guesthouse
40–70 rooms with lighting, one lift and split-unit air conditioning on essential circuits.
Clinic or small hospital
Theatre, cold chain, sterilisation and ward lighting. Usually on an ATS with a dedicated essential board.
Retail or supermarket
Refrigeration is the block load on transfer. Size the alternator for the compressor restart, not the running kW.
Workshop or light plant
70–90 kW of connected machinery. Check the largest direct-on-line motor against the 10% overload window.
Office floor
900–1,200 m² of office with HVAC, servers and lighting. Split HVAC off the essential board if the budget is tight.
Water pumping station
Two or three pumps with soft starters. Pump starting torque, not running kW, sets the rating here.

What Does a 150 kVA Generator Cost?

We quote this rating against the engine and alternator you specify rather than publishing a catalogue band, because the same 150 kVA frame spans a wide range between a Weichai build and a Cummins or Perkins build. What we need to give you a usable number: the load list or the standby kVA you are sizing to, the voltage and frequency, open skid or canopy, and the destination port. The quote then carries the engine model, alternator model and the load-bank test sheet — not a range.

150 kVA Generator Questions

How many amps does a 150 kVA generator deliver?

217 A per phase at 400 V three-phase, 228 A at 380 V, 209 A at 415 V, 180 A at 480 V. Size the breaker at 125% of the 400 V figure — 271 A, so a 320 A frame.

Is 150 kVA the same as 120 kW?

At 0.8 power factor, yes — 150 × 0.8 = 120 kW. If the site power factor is lower than 0.8, the usable kW drops below 120 and the rating needs rechecking against the load list.

How much fuel does a 150 kVA generator use per hour?

27.6 L/h at full 150 kVA load, 13.8 L/h at half load. That is about 0.184 L per kVA per hour — consumption tracks load almost linearly in this class.

What is the difference between 150 kVA and 187 kVA?

187 kVA is the same frame described in kW rather than kVA: 150 kW at 0.8 PF equals 187 kVA. If a tender asks for 150 kW, quote 187 kVA. If it asks for 150 kVA, that is 120 kW — the smaller set. Getting this backwards is the most common sizing error we see.

Can a 150 kVA set run a 90 kW motor direct-on-line?

Only if it is the largest load and the set is sized for the starting current. A 90 kW DOL motor draws roughly 6–7 times full-load current for 3–8 seconds. Either fit a soft starter or star-delta, or move up to 200 kVA. Send us the motor list and we will check the dip.

How many hours can a 150 kVA set run on a baseframe tank?

A 400 L baseframe tank gives 14.5 h at full load and 29.0 h at half load. Tanks are built to the order, so specify from the runtime you need rather than picking a standard size.

What does a 150 kVA generator cost?

It depends on the engine and alternator you specify. We quote against your load list and destination port rather than publishing a catalogue band, because the same 150 kVA frame spans a wide price range between a Weichai build and a Cummins or Perkins build.