Status: IN STOCK, Same day shipping Worldwide available | Brand New, 1 Year International Warranty
* Contact us for pricing and full specifications
| SKU | DSR |
| Brand | MECC ALTE |
| Model Number | DSR |
| Regulator Type | Analogue Automatic Voltage Regulator |
| Excitation System | Self-excited, shunt fed |
| Sensing Input | Single-phase sensing |
| Power Input | From the main stator, 50 / 60 Hz |
| Output Voltage | 63 Vdc class |
| Continuous Field Current | 4-6 A class |
| Forcing Current | Short-term forcing current available for load steps |
| Field Resistance (Min) | Matched to the exciter field |
| Regulation Accuracy | +/-1.0 per cent |
| Response Time | Standard analogue response |
| Frequency Range | 50 / 60 Hz |
| Under-Frequency Protection | Not published for this model - ask us for the nameplate data |
| Voltage Adjustment | Internal trim potentiometer |
| Paralleling / Droop | Reactive droop via CT |
| Build-Up Voltage | Builds up from residual voltage |
| Thermal Drift | Low thermal drift |
| Operating Temperature | -20 to +60 degC |
| Storage Temperature | -40 to +85 degC |
| Protection Features | Over-excitation |
| Compatible Alternators | Mecc Alte and compatible brushless alternators |
| Mounting | Panel or terminal-box mount |
| Dimensions (L x W x H) | Approximately 145 x 95 x 45 mm |
| Weight | Approximately 0.35 kg |
| Lifecycle Status | Legacy, replaced by UVR6 on new build |
| Availability | IN STOCK, Same day shipping Worldwide available |
| Condition | Brand New, 1 Year International Warranty |
| Warranty | 1 Year International Warranty |
What the DSR is. A Analogue Automatic Voltage Regulator built by MECC ALTE for brushless excitation systems. On paper the specification is a list; in service it is a set of limits. The current the board will hold indefinitely is 4-6 A class; the field resistance window it will drive without exceeding its output voltage is Matched to the exciter field; the tightest voltage band it can maintain is +/-1.0 per cent; and the ambient range in which all of that remains true is -20 to +60 degC.
Excitation architecture. Self-excited, shunt fed. That single sentence decides most of the regulator's behaviour in a fault: whether the field survives a close-up short circuit, whether the machine builds up from residual voltage on its own, and how much the terminal voltage dips when a large motor starts on the same bus. An alternator that has been rewound needs its field resistance re-measured, because a rewind commonly moves it by ten to twenty per cent in either direction.
Sensing. Single-phase sensing. The sensing circuit is the regulator's only view of the outside world, so its wiring matters as much as its specification. A voltage error introduced by a loose terminal or a long run of untwisted cable is indistinguishable, from the regulator's point of view, from a genuine voltage error on the alternator. Static accuracy is measured on a resistive load at constant frequency. Real loads and real governors are neither, so treat the figure as a comparison between boards rather than a promise.
Power stage and field drive. Power input From the main stator, 50 / 60 Hz, output 63 Vdc class. Field current rating 4-6 A class, forcing capability Short-term forcing current available for load steps, field resistance window Matched to the exciter field. These are not independent numbers: the output voltage ceiling and the field resistance together set the maximum current the board can actually deliver, and the continuous rating is only reachable at the low end of the resistance window. If the machine will not hold voltage at all, disconnect the field and measure the sensing voltage first. That one reading separates a sensing fault from a field fault.
Accuracy and response. +/-1.0 per cent steady-state accuracy, Standard analogue response, thermal drift Low thermal drift. In practice the accuracy figure is the least interesting of the three. What an operator notices is recovery after a load step, which is governed by response and by available forcing current, and what a maintenance engineer notices after two years is drift, which is governed by the reference circuit and the ambient temperature inside the terminal box. If two identical sets behave differently on the same load, swap the regulators before swapping anything else. The result tells you which side of the machine the fault is on.
Frequency behaviour. Rated for 50 / 60 Hz, with Not published for this model - ask us for the nameplate data. The frequency-sensitive function exists to protect the prime mover, not the alternator: as engine speed falls the regulator reduces excitation so the alternator stops demanding torque the engine cannot supply. Without it, an overloaded engine is dragged down until it stalls, and the alternator is blamed for a fault that belongs to the fuel or governor system. The trim potentiometer is not a calibration device. If rated voltage is not reachable near the middle of its range, the sensing tap is wrong.
Paralleling. Reactive droop via CT. On a single set this circuit does nothing. On two or more sets it is the only thing that stops the machines from exchanging reactive power in a slow oscillation, and it is the first place to look when a parallel installation shows a circulating current that nobody can explain. Load sharing between parallel sets is set up with an instrument, not by ear. A droop adjustment made by listening to the sets will be wrong at every load other than the one it was set at.
Protection built into the regulator. Over-excitation. These functions protect the alternator and the regulator, not the installation. Downstream protection, loss of mains and reverse power all belong to the controller, and a site that relies on the AVR for them is a site that will eventually trip in a way nobody can explain. Where a spare is being held, hold the drawing with it. A board without its wiring diagram costs a shift of production time to install.
What it fits. Mecc Alte and compatible brushless alternators. Lifecycle status: Legacy, replaced by UVR6 on new build. Both halves of that sentence matter at order time. A board that fits perfectly but has been discontinued is a different commercial decision from one that fits and is in current production, and the price difference rarely reflects the difference in risk. Static accuracy is measured on a resistive load at constant frequency. Real loads and real governors are neither, so treat the figure as a comparison between boards rather than a promise.
Field notes on this model. This is one of the older Mecc Alte analogue boards, still found on machines in service and still worth carrying as a spare, because a failed AVR is the single most common reason a healthy alternator goes off line.
What the customer is actually buying. When a regulator is quoted as a replacement, the buyer is not purchasing a circuit board. They are purchasing the certainty that the set will hold voltage on the next load step. On the DSR that certainty comes from the combination of 4-6 A class continuous field current and the Standard analogue response response, and it disappears the moment the field resistance drifts outside the window the board was set up for.
Earthing and shielding. The regulator reference is the machine frame. Bond the AVR mounting plate to the frame with a dedicated conductor rather than relying on the mounting screws, and earth the sensing cable shield at one end only. When a set shows a voltage that wanders slowly with no load change, the cause is usually a circulating current in the shield rather than a failing board.
Paralleling setup. With two sets on the bus, adjust droop until reactive load divides in proportion to machine rating, then check it again at half load. A droop setting that looks right at full load and wrong at half load is usually a CT ratio error rather than a regulator fault.
Measure, do not assume. Nameplate field resistance figures are nominal at 20 degC and are frequently wrong after a rewind. Take the measurement with a four-wire meter if one is available, because a two-wire reading on a low resistance winding includes the lead resistance and can be off by twenty per cent.
Voltage high and unresponsive. If the machine runs to maximum excitation regardless of the trim, disconnect the field and see whether the voltage collapses. If it does, the regulator has failed shorted; if it does not, the field is being fed from somewhere else, usually a shorted thyristor or a mis-wired paralleling circuit. Do not run the machine at full excitation for more than a few seconds while diagnosing, because the winding will not survive it.
Part numbers are not interchangeable across suffixes. On this family the suffix carries the field current class, the sensing arrangement or the frequency band, and two boards that look identical in a photograph can be a hundred per cent different in rating. Quote the full model number including the suffix, and where the suffix is unclear send a photograph of the original board with the terminal markings visible.
What the customer is actually buying. When a regulator is quoted as a replacement, the buyer is not purchasing a circuit board. They are purchasing the certainty that the set will hold voltage on the next load step. On the DSR that certainty comes from the combination of 4-6 A class continuous field current and the Standard analogue response response, and it disappears the moment the field resistance drifts outside the window the board was set up for.
Earthing and shielding. The regulator reference is the machine frame. Bond the AVR mounting plate to the frame with a dedicated conductor rather than relying on the mounting screws, and earth the sensing cable shield at one end only. When a set shows a voltage that wanders slowly with no load change, the cause is usually a circulating current in the shield rather than a failing board.
Jinjia Power Equipment Co., Ltd | Address: No.737, Guanzhang Road, Liaobu Town, Dongguan, China
Phone: 86-13553838770 | 86-0769-89610677 | info@jinjiadongli.com
Jinjia Power, Quality Assured