Status: IN STOCK, Same day shipping Worldwide available | Brand New, 3 Years International Warranty
Volume, OEM and project pricing available on request.
| SKU | PI734F 3-Phase |
| Brand | Stamford |
| Series | Stamford PI |
| Frame | 734 |
| Core length | F |
| Phase | Three phase |
| Poles | 2-pole |
| Rated power | 2200 kW |
| Apparent power | 2750 kVA at 0.8 PF |
| Rated voltage | 400 V |
| Rated current | 3969.3 A |
| Frequency | 50 Hz |
| Power factor | 0.8 |
| Rated speed | 3000 rpm |
| Insulation class | Class H |
| Ingress protection | IP23 |
| Excitation system | self-excited, brushless |
| Voltage regulator | AS480 (+/-1.0%) |
| Voltage regulation | +/-1.0% |
| Bearing | BALL.6309-2RS drive end / BALL.6306-2RS non-drive end (PI144) |
| Winding connection | 12 re-connectable |
| Maximum overspeed | 2250 rpm |
| Frequency | 50 Hz |
| Rated speed | 3000 rpm |
| Core stack position | 6 of 7 in PI family |
| Adjacent ratings | PI734E 3-Phase at 1900 kW / PI734G 3-Phase at 2300 kW |
| Altitude | 1000 m |
| Standards | BS EN 60034, BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA C22.2-100, AS1359 |
| Availability | IN STOCK, Same day shipping Worldwide available |
| Condition | Brand New, 3 Years International Warranty |
Jinjia Power Equipment Co., Ltd | Address: No.737, Guanzhang Road, Liaobu Town, Dongguan, China
Phone: 86-13553838770 | 86-0769-89610677 | info@jinjiadongli.com
Jinjia Power, Quality Assured
The PI734F 3-Phase is rated at 2200 kW (2750 kVA at 0.8 PF). The kW figure is the mechanical shaft input it accepts; the kVA figure is the electrical output at the stated power factor. Size the engine against the kW figure with a margin for the alternator's efficiency, and size the load against the kVA figure.
Rated output is 400 V at 50 Hz, Three phase. The winding is 12 re-connectable. Check the winding connection before ordering if your site runs a different voltage β a reconnectable unit can be rewired, a fixed-winding unit cannot.
Rated current is 3969.3 A at 400 V, Three phase. Use this figure when sizing cables, circuit breakers and the transfer switch β the breaker is set against the alternator's rated current, not the engine's.
It is a 2-pole machine running at 3000 rpm, 50 Hz. Pole count and speed are linked: a 4-pole machine at 50 Hz turns at 1500 rpm and at 60 Hz at 1800 rpm. The speed is fixed by the frequency, so the same frame cannot be run at an arbitrary speed.
Insulation is Class H and the enclosure is rated IP23. Maximum overspeed is 2250 rpm. Class H insulation is rated for a 180 Β°C rise limit and gives margin for hot plant rooms; the IP rating states what the enclosure keeps out β IP23 protects against falling water at up to 60Β° from vertical, not against immersion.
Excitation is self-excited, brushless, regulated by AS480 (+/-1.0%). Voltage regulation is held to +/-1.0%. A brushless, self-excited machine has no slip rings to maintain, which is why it is the default for standby plant. The AVR is the part that holds voltage steady under changing load β if voltage wanders under load, the AVR is the first thing to check.
Voltage regulation is +/-1.0% from no load to full load at the stated power factor. That is the steady-state figure; transient dips when a large motor starts are larger and are handled by the engine's response and the AVR's forcing capability, not by the regulation figure alone.
Bearing arrangement is BALL.6309-2RS drive end / BALL.6306-2RS non-drive end (PI144). A single-bearing machine couples directly to the engine flywheel housing and needs no separate bedplate alignment; a two-bearing machine carries its own bearing and couples through a flexible coupling. Confirm which your engine expects before ordering.
Winding connection is 12 re-connectable. A 12-wire reconnectable machine can be wired in series or parallel, star or delta, to deliver several voltage combinations from the same alternator. If your market runs a voltage not listed on this page, send it and we will confirm whether the winding covers it.
It is built to BS EN 60034, BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA C22.2-100, AS1359. These are the design and test standards the machine is verified against, not a certification mark β the test record and the manufacturer's declaration travel with the unit so your commissioning file is complete.
The frame code 734 identifies the mechanical size of the machine in the Stamford PI range, and the core sits 6 of 7 in PI family. Within one frame the core length letter steps from short to long, and each step adds lamination stack and therefore output without changing the mounting dimensions. That is why two alternators with the same frame but different core letters are physically interchangeable but electrically different.
In the same frame family, PI734E 3-Phase at 1900 kW / PI734G 3-Phase at 2300 kW. Because the mounting dimensions are shared, stepping one core length up or down is usually a direct swap β useful when a load calculation lands between two catalogue ratings. Confirm the engine can carry the higher figure before you step up.
The rating assumes an installation altitude of 1000 m. Above that, cooling air is thinner and the machine must be derated β roughly 1% of output per additional 100 m. If your site is higher, tell us the altitude and we will quote the next frame up rather than let the alternator run hot.
IN STOCK, Same day shipping Worldwide available. Condition: Brand New, 3 Years International Warranty. Consumables and common frame sizes ship from stock; less common windings are built to order. Send the engine model and the required voltage and we will confirm fitment against your set before the order is placed.