86-0769-89610677 / 86-13553838770 | info@jinjiadongli.com
Home > AC ALTERNATORS > LSA 49.1M75 3-Phase - Leroy Somer | 800 kW
LSA 49.1M75 3-Phase Leroy Somer 800 kW 1000 kVA Three phase AC alternator | Jinjia Power

LSA 49.1M75 3-Phase - Leroy Somer | 800 kW

LSA 49.1M75-3-PHASE

Status: IN STOCK, Same day shipping Worldwide available | Brand New, 3 Years International Warranty

Volume, OEM and project pricing available on request.

πŸ“ž Get a Quote:86-13553838770
← Back to products

Specifications

SKULSA 49.1M75 3-Phase
BrandLeroy Somer
SeriesLeroy Somer LSA
Frame49.1
Core lengthM75
PhaseThree phase
Poles4-pole
Rated power800 kW
Apparent power1000 kVA at 0.8 PF
Rated voltage400 V
Rated current1443.4 A
Frequency50 Hz
Power factor0.8
Rated speed1500 rpm
Insulation classClass H
Ingress protectionIP23
Excitation systemSHUNT (R250) standard; AREP (R450 / D510C) or PMG optional
Voltage regulatorR250 shunt / R450 AREP / D510C AREP
Voltage regulation+/-0.5%
Bearingpermanently lubricated ball bearings
Winding connection6 or 12 re-connectable
Maximum overspeed2250 rpm
Frequency50 Hz
Rated speed1500 rpm
Core stack position3 of 4 in LSA family
Adjacent ratingsLSA 49.1M6 3-Phase at 700 kW / LSA 50S4 3-Phase at 900 kW
Altitude1000 m without derating
StandardsIEC 60034, NEMA MG1-32 & 33, ISO 8528-3, CSA C22.2 No.100-14, UL 1446, UL 1004-1/1004-4
AvailabilityIN STOCK, Same day shipping Worldwide available
ConditionBrand New, 3 Years International Warranty

Product Overview

Model. The LSA 49.1M75 3-Phase is a Leroy Somer LSA 4-pole alternator. In Leroy Somer's LSA nomenclature 49.1 is the frame and M75 is the core length: the frame fixes the stator bore and shaft centre height, and the core code fixes how much active iron is stacked into that bore. This one uses the medium core, stack position 75 within that family. A longer core in the same frame buys more output at the same temperature rise, which is why the same frame number appears across a spread of ratings. It is wound for three-phase service at 50 Hz. Electrical rating. At 0.8 power factor lagging this machine is rated 800 kW, which is 1000 kVA, delivered as three-phase at 400 V 50 Hz. At 400 V line-to-line that is 1443.4 A per line. Ratings in this band are usually specified with a 1.25 service factor margin over the prime kW of the driving engine, so the alternator is not the limiting item when the set is asked to carry a block load. The 1500 rpm figure is synchronous speed, so there is no slip and no speed-dependent voltage droop. Frame and core. The 49.1 frame carries the M75 core. Frame size fixes the stator bore and the shaft centre height; the core length fixes how much active iron sits in that bore, and therefore how much output the machine can make at a given temperature rise. The exact finished weight and outline drawing depend on the winding and the coupling, so they are confirmed on the certified datasheet issued with the order. The cooling circuit is direct air cooled, IC01, 0.9 m3/s at 47.2 frame, and the frame is steel frame with cast iron end shields. Three-phase winding. This is a three-phase machine with a 6 or 12 re-connectable winding brought out to 6 or 12 re-connectable terminals, so it can be reconnected on site for the usual voltage pairs β€” 380/220 V, 400/230 V, 415/240 V, 440/254 V and 480/277 V on the 50 Hz build, and the 60 Hz pairs on the 60 Hz build. Reconnection is done on the link board inside the terminal box, not by rewinding, which is why one machine can serve a 380 V job and a 480 V job. The 2/3 pitch design is what keeps the fifth and seventh space harmonics down without skewing the stator, and it is the reason the line-to-line waveform stays within the distortion limits the standards ask for. Four-pole build. A four-pole machine turns at 1500 rpm on 50 Hz and 1800 rpm on 60 Hz. That is the standard choice for generator sets from a few tens of kVA up to the low megawatt range, because the lower rotor speed gives a longer bearing life, a quieter fan, a higher subtransient reactance that is easier to coordinate with downstream protection, and a rotor that can carry a substantial damper cage for parallel operation. The trade is weight: a four-pole machine of a given kVA is roughly twice the mass of a two-pole one. Excitation and voltage regulation. The excitation system is SHUNT (R250) standard; AREP (R450 / D510C) or PMG optional, regulated by R250 shunt / R450 AREP / D510C AREP, holding steady-state voltage to +/-0.5%. Leroy Somer builds the LSA around three excitation levels. Plain SHUNT excitation with the R250 regulator is the default and is entirely adequate for a single set carrying a stable load. AREP β€” the Auxiliary winding, Regulated, Excitation, Protection arrangement, run through the R450 or D510C regulator β€” adds a separate auxiliary stator winding that keeps the excitation supply independent of the main output voltage, so the machine sustains about 300% of full load current into a short circuit for up to ten seconds. That is what lets a downstream breaker clear a fault selectively. PMG excitation goes one step further with a permanent magnet pilot exciter and is normally specified where the load is heavily non-linear or where the set has to ride through a sustained fault. Mechanical build. The frame is steel frame with cast iron end shields. Bearings are permanently lubricated ball bearings. Mounting is IM 1201 (single bearing, SAE flange + drive discs) or IM 1001 (two bearing, SAE flange + keyed shaft). Maximum overspeed is 2250 rpm, and the machine is rated for 1000 m without derating. The rotor is dynamically balanced to ISO 1940 and IEC 60034-14. The single-bearing arrangement couples through a SAE flange and drive discs, so the alternator rotor is carried partly by the engine flywheel housing; the two-bearing arrangement carries its own shaft extension and takes a conventional coupling. Where it fits. Heavy industrial and mining duty: crushers, conveyors, mill drives, and large pumping stations. These are the jobs where the machine runs continuously at high load and where bearing life and winding temperature rise, not nameplate kVA, decide how long it lasts. On a three-phase machine of 800 kW the practical constraint is usually the downstream protection and the cable, not the alternator itself. Core stack position. The M75 core is stack position 3 of 4 in the LSA family, roughly 75% of the way along the family's lamination length range. It sits between the shorter M6 and the longer L9. Long-stack builds carry the rating in the frame with the lowest flux density of the family. The extra iron costs length and weight, and buys a cooler-running core, lower magnetising current, better part-load efficiency and more margin for site ambient above 40 C or for a non-standard voltage. Where it sits in the range. The LSA family is catalogued from 6.4 kW up to 1680 kW, and this page covers the 800 kW / 1000 kVA point. The step below it is the LSA 49.1M6 3-Phase at 700 kW, 875 kVA. The step above it is the LSA 50S4 3-Phase at 900 kW, 1125 kVA. If your load sits between two steps, take the higher one and let the engine run at part load rather than pushing the smaller machine to its limit on a hot afternoon. Reading the model code. A Leroy Somer designation is read as the LSA or TAL series, the frame size, and the core stack code (VS, S, M, L or VL plus a stack number). Here that gives LSA 49.1M75 3-Phase for the model, 49.1 for the frame, M75 for the core and three for the phase count, so the code on the nameplate and the code on this page match one for one. Quoting the full code rather than just the frame matters on this family, because the same frame number is built in several core lengths and the winding changes with the voltage. What the nameplate means once it is wired in. At 800 kW and 1000 kVA this machine pushes 1443 A down each line on a 400 V three-phase supply. That current, not the kVA figure, is what the switchgear and the cable have to survive, so the outgoing breaker should be a 2000 A frame device set to trip above 1804 A, and the run from the alternator terminals to the first panel should be 500 mm2 copper per phase for a normal 25 to 30 m span. Longer runs, aluminium conductors or tray-installed cable all move that number up, and the volt drop at full load is what decides it in the end. On the mechanical side the prime mover has to deliver about 896 kW at the coupling. The usual 1.10 to 1.15 margin over the alternator rating covers the fan, the excitation loss and the governor droop, and it is the reason a 800 kW alternator is normally quoted against a 896 kW engine rather than a 800 kW one. Fuel burn follows the electrical load almost linearly in this range. At a realistic 0.29 L per kWh for a modern common-rail set, running this alternator at full rating takes roughly 232 L per hour; at 75 per cent load it drops to about 181 L per hour and at half load to about 128 L per hour, because the fixed losses stay put while the variable ones fall away. Quote the breaker frame, the cable size and the engine rating together with the alternator, because a set that is right on paper and undersized on the cable is the most common way a good alternator gets blamed for a bad installation. Where this rating sits in the frame ladder. Within the 49.1 frame LSA carries 4 distinct ratings, and this is number 3 of them at 800 kW. The step below is the LSA 49.1M6 3-Phase at 700 kW / 875 kVA, 100 kW under this one; the step above is the LSA 49.1L9 3-Phase at 900 kW / 1125 kVA, 100 kW over it. Every step inside one frame is one more lamination stack length. The shaft, the bearings, the foot pattern, the terminal box and the AVR are the same part across the whole ladder, and only the core length and the winding change. That is why the price gap between two neighbouring steps is small while the gap between the last step of one frame and the first step of the next is large. It also sets the value-engineering rule: dropping one core size inside the frame saves money and axial length but eats the margin to the load, while stepping up one size costs far less than jumping to the next frame and buying a bigger skid, a bigger breaker and a bigger cable with it. Supply. Supplied as a genuine Leroy Somer unit β€” Nidec Industrial Solutions, built in France. LSA and TAL ranges are built in Europe and carry a European certificate of origin. Each alternator ships with the routine test certificate, the winding connection diagram, and the AVR commissioning sheet. Export packing is seaworthy plywood on a pallet sized to the frame, and the machine is strapped and shrink-wrapped inside it. Tell us the engine make and model, the coupling arrangement (single or two bearing), the voltage and frequency, and whether you need a PMG, and we will confirm the build before it leaves the works.

Jinjia Power Equipment Co., Ltd | Address: No.737, Guanzhang Road, Liaobu Town, Dongguan, China

Phone: 86-13553838770 | 86-0769-89610677 | info@jinjiadongli.com

Jinjia Power, Quality Assured

Frequently Asked Questions

What is the rated output of the LSA 49.1M75 3-Phase alternator?

The LSA 49.1M75 3-Phase is rated at 800 kW (1000 kVA at 0.8 PF). The kW figure is the mechanical shaft input it accepts; the kVA figure is the electrical output at the stated power factor. Size the engine against the kW figure with a margin for the alternator's efficiency, and size the load against the kVA figure.

What voltage and frequency does the LSA 49.1M75 3-Phase produce?

Rated output is 400 V at 50 Hz, Three phase. The winding is 6 or 12 re-connectable. Check the winding connection before ordering if your site runs a different voltage β€” a reconnectable unit can be rewired, a fixed-winding unit cannot.

What is the rated current of the LSA 49.1M75 3-Phase?

Rated current is 1443.4 A at 400 V, Three phase. Use this figure when sizing cables, circuit breakers and the transfer switch β€” the breaker is set against the alternator's rated current, not the engine's.

How fast does the LSA 49.1M75 3-Phase run and how many poles does it have?

It is a 4-pole machine running at 1500 rpm, 50 Hz. Pole count and speed are linked: a 4-pole machine at 50 Hz turns at 1500 rpm and at 60 Hz at 1800 rpm. The speed is fixed by the frequency, so the same frame cannot be run at an arbitrary speed.

What insulation class and ingress protection does the LSA 49.1M75 3-Phase have?

Insulation is Class H and the enclosure is rated IP23. Maximum overspeed is 2250 rpm. Class H insulation is rated for a 180 Β°C rise limit and gives margin for hot plant rooms; the IP rating states what the enclosure keeps out β€” IP23 protects against falling water at up to 60Β° from vertical, not against immersion.

What excitation system and voltage regulator does the LSA 49.1M75 3-Phase use?

Excitation is SHUNT (R250) standard; AREP (R450 / D510C) or PMG optional, regulated by R250 shunt / R450 AREP / D510C AREP. Voltage regulation is held to +/-0.5%. A brushless, self-excited machine has no slip rings to maintain, which is why it is the default for standby plant. The AVR is the part that holds voltage steady under changing load β€” if voltage wanders under load, the AVR is the first thing to check.

How stable is the voltage output of the LSA 49.1M75 3-Phase?

Voltage regulation is +/-0.5% from no load to full load at the stated power factor. That is the steady-state figure; transient dips when a large motor starts are larger and are handled by the engine's response and the AVR's forcing capability, not by the regulation figure alone.

What bearing does the LSA 49.1M75 3-Phase use?

Bearing arrangement is permanently lubricated ball bearings. A single-bearing machine couples directly to the engine flywheel housing and needs no separate bedplate alignment; a two-bearing machine carries its own bearing and couples through a flexible coupling. Confirm which your engine expects before ordering.

Can the LSA 49.1M75 3-Phase be reconnected for a different voltage?

Winding connection is 6 or 12 re-connectable. A 12-wire reconnectable machine can be wired in series or parallel, star or delta, to deliver several voltage combinations from the same alternator. If your market runs a voltage not listed on this page, send it and we will confirm whether the winding covers it.

What standards does the LSA 49.1M75 3-Phase meet?

It is built to IEC 60034, NEMA MG1-32 & 33, ISO 8528-3, CSA C22.2 No.100-14, UL 1446, UL 1004-1/1004-4. These are the design and test standards the machine is verified against, not a certification mark β€” the test record and the manufacturer's declaration travel with the unit so your commissioning file is complete.

What do the 49.1 and M75 designations mean?

The frame code 49.1 identifies the mechanical size of the machine in the Leroy Somer LSA range, and the core sits 3 of 4 in LSA family. Within one frame the core length letter steps from short to long, and each step adds lamination stack and therefore output without changing the mounting dimensions. That is why two alternators with the same frame but different core letters are physically interchangeable but electrically different.

What is the nearest alternative rating to the LSA 49.1M75 3-Phase?

In the same frame family, LSA 49.1M6 3-Phase at 700 kW / LSA 50S4 3-Phase at 900 kW. Because the mounting dimensions are shared, stepping one core length up or down is usually a direct swap β€” useful when a load calculation lands between two catalogue ratings. Confirm the engine can carry the higher figure before you step up.

What altitude is the LSA 49.1M75 3-Phase rated for?

The rating assumes an installation altitude of 1000 m without derating. Above that, cooling air is thinner and the machine must be derated β€” roughly 1% of output per additional 100 m. If your site is higher, tell us the altitude and we will quote the next frame up rather than let the alternator run hot.

Is the LSA 49.1M75 3-Phase in stock, and what warranty comes with it?

IN STOCK, Same day shipping Worldwide available. Condition: Brand New, 3 Years International Warranty. Consumables and common frame sizes ship from stock; less common windings are built to order. Send the engine model and the required voltage and we will confirm fitment against your set before the order is placed.