86-0769-89610677 / 86-13553838770 | info@jinjiadongli.com
Home > AC ALTERNATORS > 431PSL6226 1-Phase - Marathon | 175 kW
431PSL6226 1-Phase Marathon 175 kW 218.8 kVA Single phase AC alternator | Jinjia Power

431PSL6226 1-Phase - Marathon | 175 kW

431PSL6226-1-PHASE

Status: IN STOCK, Same day shipping Worldwide available | New

* Contact us for pricing and full specifications

πŸ“ž Get a Quote:86-13553838770
← Back to products

Specifications

SKU431PSL6226 1-Phase
BrandMarathon
SeriesMarathon PSL
Frame431
Core length6226
PhaseSingle phase
Poles4-pole
Rated power175 kW
Apparent power218.8 kVA at 0.8 PF
Rated voltage240 V
Rated current911.5 A
Frequency60 Hz
Power factor0.8
Rated speed1800 rpm
Insulation classNEMA Class H
Ingress protectionIP22 / IP23
Excitation systemself-excited brushless with SE350E AVR
Voltage regulatorSE350E standard / PM500 / DVR2400 with PMG
Voltage regulation+/-1.0%
Bearingsealed for life ball bearings
Winding connection12 re-connectable
Maximum overspeed2250 rpm
Outline dimensionsA 21.46 in | B 15.00 | BA 10.00 | C 33.89 (C w/PMG 38.27) | D 22.64 | E 9.00 | 2F 11.00 | H 13.00 | P 24.97 | X 36.10 | Y 16.00 | Z 2.66
Frequency60 Hz
Rated speed1800 rpm
Core stack position3 of 3 in PSL family
Adjacent ratings431PSL6224 1-Phase at 150 kW / 432PSL6228 1-Phase at 225 kW
Altitude1000 m
StandardsNEMA MG1-32, UL 1004, CSA C22.2 No.100, IEC 60034
AvailabilityIN STOCK, Same day shipping Worldwide available
ConditionBrand New, 3 Years International Warranty

Product Overview

Model. The 431PSL6226 1-Phase is a Marathon PSL 4-pole alternator. Marathon reads the model as frame 431 followed by the PSL family code and the winding number 6226. The frame sets the mechanical envelope and the family code sets whether the machine is wound for single-phase or three-phase service. It is wound for single-phase service at 60 Hz. Electrical rating. At 0.8 power factor lagging this machine is rated 175 kW, which is 218.8 kVA, delivered as single-phase at 240 V 60 Hz. At 240 V that is 911.5 A through the line and the neutral. This is the band where motor starting, not steady-state kW, usually sizes the machine: a direct-on-line motor of roughly 30% of the alternator kVA will pull the terminal voltage down by about 15% at start, which is normally acceptable, and anything larger needs a soft starter or a bigger frame. The 1800 rpm figure is synchronous speed, so there is no slip and no speed-dependent voltage droop. Frame and core. The 431 frame carries the 6226 core. Frame size fixes the stator bore and the shaft centre height; the core length fixes how much active iron sits in that bore, and therefore how much output the machine can make at a given temperature rise. The exact finished weight and outline drawing depend on the winding and the coupling, so they are confirmed on the certified datasheet issued with the order. Outline dimensions in inches: A 21.46 in | B 15.00 | BA 10.00 | C 33.89 (C w/PMG 38.27) | D 22.64 | E 9.00 | 2F 11.00 | H 13.00 | P 24.97 | X 36.10 | Y 16.00 | Z 2.66. The cooling circuit is direct air cooled, IC01, and the frame is rolled steel frame, cast iron end brackets. Single-phase winding. This is a single-phase machine, so the winding is laid out to produce one sinusoid across the output terminals rather than a three-phase set. Single-phase alternators of this size are almost always fitted with a capacitor or a compounded excitation arrangement to hold the voltage steady as the load swings, because the pulsating armature reaction of a single-phase load pulls the terminal voltage around far more than a balanced three-phase load does. The practical consequence for the buyer is that single-phase kVA and three-phase kVA of the same frame are not interchangeable: the single-phase machine is derated for the same iron, and the wiring, the circuit breaker and the cable all have to be sized on the single-phase current, which is roughly 1.7 times the three-phase current for the same kVA at the same voltage. Four-pole build. A four-pole machine turns at 1500 rpm on 50 Hz and 1800 rpm on 60 Hz. That is the standard choice for generator sets from a few tens of kVA up to the low megawatt range, because the lower rotor speed gives a longer bearing life, a quieter fan, a higher subtransient reactance that is easier to coordinate with downstream protection, and a rotor that can carry a substantial damper cage for parallel operation. The trade is weight: a four-pole machine of a given kVA is roughly twice the mass of a two-pole one. Excitation and voltage regulation. The excitation system is self-excited brushless with SE350E AVR, regulated by SE350E standard / PM500 / DVR2400 with PMG, holding steady-state voltage to +/-1.0%. Marathon fits the SE350E as the standard regulator on the smaller frames, with the PM500 and the DVR2400 available where a PMG is specified. On the Mariner and harsh-duty builds the excitation stator is fully encapsulated and the rotating rectifier is a heavy-duty assembly with a 300% diode margin and sealed welded stud terminations, which is the difference between a machine that survives a damp boat hold and one that does not. Mechanical build. The frame is rolled steel frame, cast iron end brackets. Bearings are sealed for life ball bearings. Mounting is single bearing SAE flange or two bearing. Maximum overspeed is 2250 rpm, and the machine is rated for 1000 m. On the 280 to 430 frames the machine ships with twelve leads and a link board as standard, and the minimum inlet clearance is six inches. On the 570 frame and above the terminal box is mounted on top with the link board inside it, and a selenium surge suppressor is fitted as standard from the 360 frame up. Harsh-duty builds get multiple dip-and-bake cycles on the main stator. Where it fits. Industrial plant and institutional standby: a hospital theatre block, a small data room, a food processing line, or a water treatment works. These jobs usually ask for a PMG or AREP excitation system so that the downstream protection can discriminate on a fault. On a single-phase machine of 175 kW the practical constraint is usually the downstream protection and the cable, not the alternator itself. Core stack position. The 6226 core is stack position 3 of 3 in the PSL family, roughly 100% of the way along the family's lamination length range. It is the longest stack the PSL family is built with. Long-stack builds carry the rating in the frame with the lowest flux density of the family. The extra iron costs length and weight, and buys a cooler-running core, lower magnetising current, better part-load efficiency and more margin for site ambient above 40 C or for a non-standard voltage. Where it sits in the range. The PSL family is catalogued from 12 kW up to 225 kW, and this page covers the 175 kW / 218.8 kVA point. The step below it is the 431PSL6224 1-Phase at 150 kW, 187.5 kVA. The step above it is the 432PSL6228 1-Phase at 225 kW, 281.2 kVA. If your load sits between two steps, take the higher one and let the engine run at part load rather than pushing the smaller machine to its limit on a hot afternoon. Reading the model code. A Marathon designation is read as the frame number, the winding family (PSL, CSL, CSA, RSL, FSL or FDL), and a four-digit winding code. Here that gives 431PSL6226 1-Phase for the model, 431 for the frame, 6226 for the core and single for the phase count, so the code on the nameplate and the code on this page match one for one. Quoting the full code rather than just the frame matters on this family, because the same frame number is built in several core lengths and the winding changes with the voltage. Frame position. The PSL range is built on 9 frame sizes β€” 281, 282, 283, 284, 285, 286, 287, 431, 432 β€” and the 431 frame is number 8 of them. No other frame in this range carries exactly this rating, so the 431 is the only build at 175 kW and there is no cross-frame decision to make. What the nameplate means once it is wired in. At 175 kW and 218.8 kVA this machine pushes 911 A down each line on a 240 V single-phase supply. That current, not the kVA figure, is what the switchgear and the cable have to survive, so the outgoing breaker should be a 1250 A frame device set to trip above 1139 A, and the run from the alternator terminals to the first panel should be 400 mm2 copper per phase for a normal 25 to 30 m span. Longer runs, aluminium conductors or tray-installed cable all move that number up, and the volt drop at full load is what decides it in the end. On the mechanical side the prime mover has to deliver about 196 kW at the coupling. The usual 1.10 to 1.15 margin over the alternator rating covers the fan, the excitation loss and the governor droop, and it is the reason a 175 kW alternator is normally quoted against a 196 kW engine rather than a 175 kW one. Fuel burn follows the electrical load almost linearly in this range. At a realistic 0.29 L per kWh for a modern common-rail set, running this alternator at full rating takes roughly 51 L per hour; at 75 per cent load it drops to about 40 L per hour and at half load to about 28 L per hour, because the fixed losses stay put while the variable ones fall away. Quote the breaker frame, the cable size and the engine rating together with the alternator, because a set that is right on paper and undersized on the cable is the most common way a good alternator gets blamed for a bad installation. Where this rating sits in the frame ladder. Within the 431 frame PSL carries 3 distinct ratings, and this is number 3 of them at 175 kW. This is the largest rating the 431 frame carries; the step below is the 431PSL6224 1-Phase at 150 kW / 187.5 kVA, 25 kW under this one. Anything bigger moves to the next frame size up. Every step inside one frame is one more lamination stack length. The shaft, the bearings, the foot pattern, the terminal box and the AVR are the same part across the whole ladder, and only the core length and the winding change. That is why the price gap between two neighbouring steps is small while the gap between the last step of one frame and the first step of the next is large. It also sets the value-engineering rule: dropping one core size inside the frame saves money and axial length but eats the margin to the load, while stepping up one size costs far less than jumping to the next frame and buying a bigger skid, a bigger breaker and a bigger cable with it. Supply. Supplied as a genuine Marathon unit β€” Regal Rexnord, built in United States. Marathon alternators are built by Regal Rexnord in the United States. Each alternator ships with the routine test certificate, the winding connection diagram, and the AVR commissioning sheet. Export packing is seaworthy plywood on a pallet sized to the frame, and the machine is strapped and shrink-wrapped inside it. Tell us the engine make and model, the coupling arrangement (single or two bearing), the voltage and frequency, and whether you need a PMG, and we will confirm the build before it leaves the works.

Jinjia Power Equipment Co., Ltd | Address: No.737, Guanzhang Road, Liaobu Town, Dongguan, China

Phone: 86-13553838770 | 86-0769-89610677 | info@jinjiadongli.com

Jinjia Power, Quality Assured