86-0769-89610677 / 86-13553838770 | info@jinjiadongli.com
Home > AC ALTERNATORS > LSA 42.3 S4 - Leroy Somer | 37 kW
LSA 42.3 S4 Leroy Somer 37 kW 46.2 kVA Three phase AC alternator | Jinjia Power
LSA 42.3 S4 Leroy Somer 37 kW 46.2 kVA Three phase AC alternator | Jinjia Power

LSA 42.3 S4 - Leroy Somer | 37 kW

LSA 42.3 S4

Status: IN STOCK, Same day shipping Worldwide available | Brand New, 3 Years International Warranty

Volume, OEM and project pricing available on request.

πŸ“ž Get a Quote:86-13553838770
← Back to products

Specifications

SKULSA 42.3 S4
BrandLeroy Somer
SeriesLeroy Somer LSA
Frame42.3
Core lengthS4
PhaseThree phase
Poles4-pole
Rated power37 kW
Apparent power46.2 kVA at 0.8 PF
Rated voltage480 V
Rated current55.6 A
Frequency60 Hz
Power factor0.8
Rated speed1800 rpm
Insulation classClass H
Ingress protectionIP23
Excitation systemSHUNT (R250) standard; AREP (R450 / D510C) or PMG optional
Voltage regulatorR250 shunt / R450 AREP / D510C AREP
Voltage regulation+/-0.5%
Bearingpermanently lubricated ball bearings
Winding connection6 or 12 re-connectable
Maximum overspeed2250 rpm
Frequency60 Hz
Rated speed1800 rpm
Core stack position4 of 8 in LSA family
Adjacent ratingsLSA 42.3M7 3-Phase at 36 kW / LSA 42.3M8 3-Phase at 40 kW
Altitude1000 m without derating
StandardsIEC 60034, NEMA MG1-32 & 33, ISO 8528-3, CSA C22.2 No.100-14, UL 1446, UL 1004-1/1004-4
AvailabilityIN STOCK, Same day shipping Worldwide available
ConditionBrand New, 3 Years International Warranty

Product Overview

Model. The LSA 42.3 S4 is a Leroy Somer LSA 4-pole alternator. In Leroy Somer's LSA nomenclature 42.3 is the frame and S4 is the core length: the frame fixes the stator bore and shaft centre height, and the core code fixes how much active iron is stacked into that bore. This one uses the short core, stack position 4 within that family. A longer core in the same frame buys more output at the same temperature rise, which is why the same frame number appears across a spread of ratings. It is wound for three-phase service at 60 Hz. Electrical rating. At 0.8 power factor lagging this machine is rated 37 kW, which is 46.2 kVA, delivered as three-phase at 480 V 60 Hz. At 480 V line-to-line that is 55.6 A per line. Small frames like this are sensitive to load power factor: running them well below 0.8 PF pushes the field current up and the stator current up at the same kW, so the nameplate kVA is the number to design to. The 1800 rpm figure is synchronous speed, so there is no slip and no speed-dependent voltage droop. Frame and core. The 42.3 frame carries the S4 core. Frame size fixes the stator bore and the shaft centre height; the core length fixes how much active iron sits in that bore, and therefore how much output the machine can make at a given temperature rise. The exact finished weight and outline drawing depend on the winding and the coupling, so they are confirmed on the certified datasheet issued with the order. The cooling circuit is direct air cooled, IC01, 0.9 m3/s at 47.2 frame, and the frame is steel frame with cast iron end shields. Three-phase winding. This is a three-phase machine with a 6 or 12 re-connectable winding brought out to 6 or 12 re-connectable terminals, so it can be reconnected on site for the usual voltage pairs β€” 380/220 V, 400/230 V, 415/240 V, 440/254 V and 480/277 V on the 50 Hz build, and the 60 Hz pairs on the 60 Hz build. Reconnection is done on the link board inside the terminal box, not by rewinding, which is why one machine can serve a 380 V job and a 480 V job. The 2/3 pitch design is what keeps the fifth and seventh space harmonics down without skewing the stator, and it is the reason the line-to-line waveform stays within the distortion limits the standards ask for. Four-pole build. A four-pole machine turns at 1500 rpm on 50 Hz and 1800 rpm on 60 Hz. That is the standard choice for generator sets from a few tens of kVA up to the low megawatt range, because the lower rotor speed gives a longer bearing life, a quieter fan, a higher subtransient reactance that is easier to coordinate with downstream protection, and a rotor that can carry a substantial damper cage for parallel operation. The trade is weight: a four-pole machine of a given kVA is roughly twice the mass of a two-pole one. Excitation and voltage regulation. The excitation system is SHUNT (R250) standard; AREP (R450 / D510C) or PMG optional, regulated by R250 shunt / R450 AREP / D510C AREP, holding steady-state voltage to +/-0.5%. Leroy Somer builds the LSA around three excitation levels. Plain SHUNT excitation with the R250 regulator is the default and is entirely adequate for a single set carrying a stable load. AREP β€” the Auxiliary winding, Regulated, Excitation, Protection arrangement, run through the R450 or D510C regulator β€” adds a separate auxiliary stator winding that keeps the excitation supply independent of the main output voltage, so the machine sustains about 300% of full load current into a short circuit for up to ten seconds. That is what lets a downstream breaker clear a fault selectively. PMG excitation goes one step further with a permanent magnet pilot exciter and is normally specified where the load is heavily non-linear or where the set has to ride through a sustained fault. Mechanical build. The frame is steel frame with cast iron end shields. Bearings are permanently lubricated ball bearings. Mounting is IM 1201 (single bearing, SAE flange + drive discs) or IM 1001 (two bearing, SAE flange + keyed shaft). Maximum overspeed is 2250 rpm, and the machine is rated for 1000 m without derating. The rotor is dynamically balanced to ISO 1940 and IEC 60034-14. The single-bearing arrangement couples through a SAE flange and drive discs, so the alternator rotor is carried partly by the engine flywheel housing; the two-bearing arrangement carries its own shaft extension and takes a conventional coupling. Where it fits. Light commercial duty: a retail unit, a small workshop, a guesthouse, or a farm with an irrigation pump. Loads are mostly resistive and lightly inductive, so a standard shunt-excited machine copes without a PMG. On a three-phase machine of 37 kW the practical constraint is usually the downstream protection and the cable, not the alternator itself. Core stack position. The S4 core is stack position 4 of 8 in the LSA family, roughly 50% of the way along the family's lamination length range. It sits between the shorter VS3 and the longer S5. Mid-stack builds are the general-purpose choice. The lamination length is long enough to hold flux density at a moderate level and keep efficiency up at part load, while the machine still fits a standard skid or an ISO 20 ft container footprint without a custom base frame. Where it sits in the range. The LSA family is catalogued from 6.4 kW up to 1680 kW, and this page covers the 37 kW / 46.2 kVA point. The step below it is the LSA 42.3M7 3-Phase at 36 kW, 45 kVA. The step above it is the LSA 42.3M8 3-Phase at 40 kW, 50 kVA. If your load sits between two steps, take the higher one and let the engine run at part load rather than pushing the smaller machine to its limit on a hot afternoon. Reading the model code. A Leroy Somer designation is read as the LSA or TAL series, the frame size, and the core stack code (VS, S, M, L or VL plus a stack number). Here that gives LSA 42.3 S4 for the model, 42.3 for the frame, S4 for the core and three for the phase count, so the code on the nameplate and the code on this page match one for one. Quoting the full code rather than just the frame matters on this family, because the same frame number is built in several core lengths and the winding changes with the voltage. What the nameplate means once it is wired in. At 37 kW and 46.2 kVA this machine pushes 56 A down each line on a 480 V three-phase supply. That current, not the kVA figure, is what the switchgear and the cable have to survive, so the outgoing breaker should be a 100 A frame device set to trip above 70 A, and the run from the alternator terminals to the first panel should be 25 mm2 copper per phase for a normal 25 to 30 m span. Longer runs, aluminium conductors or tray-installed cable all move that number up, and the volt drop at full load is what decides it in the end. On the mechanical side the prime mover has to deliver about 41.4 kW at the coupling. The usual 1.10 to 1.15 margin over the alternator rating covers the fan, the excitation loss and the governor droop, and it is the reason a 37 kW alternator is normally quoted against a 41.4 kW engine rather than a 37 kW one. Fuel burn follows the electrical load almost linearly in this range. At a realistic 0.29 L per kWh for a modern common-rail set, running this alternator at full rating takes roughly 11 L per hour; at 75 per cent load it drops to about 8 L per hour and at half load to about 6 L per hour, because the fixed losses stay put while the variable ones fall away. Quote the breaker frame, the cable size and the engine rating together with the alternator, because a set that is right on paper and undersized on the cable is the most common way a good alternator gets blamed for a bad installation. Where this rating sits in the frame ladder. Within the 42.3 frame LSA carries 3 distinct ratings, and this is number 1 of them at 37 kW. This is the smallest rating the 42.3 frame carries; the step above is the LSA 42.3 S5 at 42 kW / 52.5 kVA, 5 kW over it. Every step inside one frame is one more lamination stack length. The shaft, the bearings, the foot pattern, the terminal box and the AVR are the same part across the whole ladder, and only the core length and the winding change. That is why the price gap between two neighbouring steps is small while the gap between the last step of one frame and the first step of the next is large. It also sets the value-engineering rule: dropping one core size inside the frame saves money and axial length but eats the margin to the load, while stepping up one size costs far less than jumping to the next frame and buying a bigger skid, a bigger breaker and a bigger cable with it. Supply. Supplied as a genuine Leroy Somer unit β€” Nidec Industrial Solutions, built in France. LSA and TAL ranges are built in Europe and carry a European certificate of origin. Each alternator ships with the routine test certificate, the winding connection diagram, and the AVR commissioning sheet. Export packing is seaworthy plywood on a pallet sized to the frame, and the machine is strapped and shrink-wrapped inside it. Tell us the engine make and model, the coupling arrangement (single or two bearing), the voltage and frequency, and whether you need a PMG, and we will confirm the build before it leaves the works.

Jinjia Power Equipment Co., Ltd | Address: No.737, Guanzhang Road, Liaobu Town, Dongguan, China

Phone: 86-13553838770 | 86-0769-89610677 | info@jinjiadongli.com

Jinjia Power, Quality Assured

Frequently Asked Questions

What is the rated output of the LSA 42.3 S4 alternator?

The LSA 42.3 S4 is rated at 37 kW (46.2 kVA at 0.8 PF). The kW figure is the mechanical shaft input it accepts; the kVA figure is the electrical output at the stated power factor. Size the engine against the kW figure with a margin for the alternator's efficiency, and size the load against the kVA figure.

What voltage and frequency does the LSA 42.3 S4 produce?

Rated output is 480 V at 60 Hz, Three phase. The winding is 6 or 12 re-connectable. Check the winding connection before ordering if your site runs a different voltage β€” a reconnectable unit can be rewired, a fixed-winding unit cannot.

What is the rated current of the LSA 42.3 S4?

Rated current is 55.6 A at 480 V, Three phase. Use this figure when sizing cables, circuit breakers and the transfer switch β€” the breaker is set against the alternator's rated current, not the engine's.

How fast does the LSA 42.3 S4 run and how many poles does it have?

It is a 4-pole machine running at 1800 rpm, 60 Hz. Pole count and speed are linked: a 4-pole machine at 50 Hz turns at 1500 rpm and at 60 Hz at 1800 rpm. The speed is fixed by the frequency, so the same frame cannot be run at an arbitrary speed.

What insulation class and ingress protection does the LSA 42.3 S4 have?

Insulation is Class H and the enclosure is rated IP23. Maximum overspeed is 2250 rpm. Class H insulation is rated for a 180 Β°C rise limit and gives margin for hot plant rooms; the IP rating states what the enclosure keeps out β€” IP23 protects against falling water at up to 60Β° from vertical, not against immersion.

What excitation system and voltage regulator does the LSA 42.3 S4 use?

Excitation is SHUNT (R250) standard; AREP (R450 / D510C) or PMG optional, regulated by R250 shunt / R450 AREP / D510C AREP. Voltage regulation is held to +/-0.5%. A brushless, self-excited machine has no slip rings to maintain, which is why it is the default for standby plant. The AVR is the part that holds voltage steady under changing load β€” if voltage wanders under load, the AVR is the first thing to check.

How stable is the voltage output of the LSA 42.3 S4?

Voltage regulation is +/-0.5% from no load to full load at the stated power factor. That is the steady-state figure; transient dips when a large motor starts are larger and are handled by the engine's response and the AVR's forcing capability, not by the regulation figure alone.

What bearing does the LSA 42.3 S4 use?

Bearing arrangement is permanently lubricated ball bearings. A single-bearing machine couples directly to the engine flywheel housing and needs no separate bedplate alignment; a two-bearing machine carries its own bearing and couples through a flexible coupling. Confirm which your engine expects before ordering.

Can the LSA 42.3 S4 be reconnected for a different voltage?

Winding connection is 6 or 12 re-connectable. A 12-wire reconnectable machine can be wired in series or parallel, star or delta, to deliver several voltage combinations from the same alternator. If your market runs a voltage not listed on this page, send it and we will confirm whether the winding covers it.

What standards does the LSA 42.3 S4 meet?

It is built to IEC 60034, NEMA MG1-32 & 33, ISO 8528-3, CSA C22.2 No.100-14, UL 1446, UL 1004-1/1004-4. These are the design and test standards the machine is verified against, not a certification mark β€” the test record and the manufacturer's declaration travel with the unit so your commissioning file is complete.

What do the 42.3 and S4 designations mean?

The frame code 42.3 identifies the mechanical size of the machine in the Leroy Somer LSA range, and the core sits 4 of 8 in LSA family. Within one frame the core length letter steps from short to long, and each step adds lamination stack and therefore output without changing the mounting dimensions. That is why two alternators with the same frame but different core letters are physically interchangeable but electrically different.

What is the nearest alternative rating to the LSA 42.3 S4?

In the same frame family, LSA 42.3M7 3-Phase at 36 kW / LSA 42.3M8 3-Phase at 40 kW. Because the mounting dimensions are shared, stepping one core length up or down is usually a direct swap β€” useful when a load calculation lands between two catalogue ratings. Confirm the engine can carry the higher figure before you step up.

What altitude is the LSA 42.3 S4 rated for?

The rating assumes an installation altitude of 1000 m without derating. Above that, cooling air is thinner and the machine must be derated β€” roughly 1% of output per additional 100 m. If your site is higher, tell us the altitude and we will quote the next frame up rather than let the alternator run hot.

Is the LSA 42.3 S4 in stock, and what warranty comes with it?

IN STOCK, Same day shipping Worldwide available. Condition: Brand New, 3 Years International Warranty. Consumables and common frame sizes ship from stock; less common windings are built to order. Send the engine model and the required voltage and we will confirm fitment against your set before the order is placed.