Home > Diesel Generators > T12K IV - SDMO - KOHLER | 10 kW 12 kVA
KOHLER | 10 kW 12 kVA Diesel Generator | Model T12K IV | Jinjia Power

T12K IV - SDMO - KOHLER | 10 kW 12 kVA

SDMO

Model: T12K IV

Power: 10KW 12KVA Standby / 8KW 11KVA Prime

Status: Brand New, 2 Years International Warranty

Volume, OEM and project pricing available on request.

📞 Get a Quote:86-13553838770
← ← Back to Products

Product Specifications

ModelT12K IV
BrandKOHLER
SeriesT series (stationary, compact)
Standby Output10 kW / 12 kVA (ESP)
Prime Output9 kW / 11 kVA (PRP)
Power Factor0.83
Phase / ConnectionThree phase, 4-wire (star)
Voltage400 V
Frequency50 Hz
Rated Speed1500 rpm
Current @ Standby17.3 A per line
Current @ Prime15.3 A per line
EngineMitsubishi S3L2-SD
Displacement1.32 L
Cylinders / Aspiration3 in line, naturally aspirated
Governormechanical
Compression Ratio22:1
Fuel TypeDiesel, EN 590 / ASTM D975 grade
Fuel Consumption @ 100%3.1 L/h (0.31 L/kWh)
Fuel Consumption @ 75%2.5 L/h
Fuel Consumption @ 50%2.1 L/h
Fuel Tank50 L (compact) / 93 L (containment)
Runtime @ 75% Load20 hours on a 50 L base tank
AlternatorAT00350T
Insulation / EnclosureClass H insulation, IP23 protection
Voltage RegulationAVR, +/- 1% steady state, THD < 3%
ControllerAPM303 (TELYS optional)
ProtectionOver-speed, low oil pressure, high coolant temperature, over/under voltage, over/under frequency, over-current, phase sequence
Starting System12 V DC electric starter, 12 V charge alternator, battery included
CoolingRadiator cooled, 40 C ambient design
Dimensions1405 x 715 x 1053 mm open / 1750 x 775 x 1230 mm M126
Dry Weight387 kg open / 530 kg M126
Noise Level71 dB(A) @ 1 m, 58 dB(A) @ 7 m
Enclosure OptionsOpen skid / weatherproof silent canopy / containerised / mobile trailer
EmissionEmission tier depends on the destination market and is confirmed per order — EU Stage V, US EPA Tier 4 Final, or unregulated where the market allows.
StandardISO 8528-1, performance class G1/G2; CE marking supported by the manufacturing plant's Declaration of Conformity
Warranty2 years or 2,000 hours, international coverage
AvailabilityIN STOCK, Same day shipping Worldwide available
ConditionBrand New, 2 Years International Warranty
QualityLoad bank tested in our Dongguan facility
ReliabilityMade in China; factory load-bank tested

Overview

T12K IV at a glance. This is a 10 kW / 12 kVA standby, 9 kW / 11 kVA prime diesel generating set built on a Kohler-SDMO platform and wound for 400 V, 50 Hz three phase output at 1500 rpm. It sits in the small stationary class where the set is bought to carry a defined load block rather than to run a plant: a shop, a guesthouse, a telecom cabinet, a small cold store, a farm pump, or the essential circuit of a house. At this rating the physical size matters as much as the numbers, which is why the same machine is offered on an open skid and inside a canopy that fits through a standard doorway.

Reading the model code. T12K IV decodes as the T prefix, the frame number 12 which tracks the kVA class, and the suffix string K. The T range uses Mitsubishi heavy-duty industrial diesels (S3L2-SD on the three-cylinder units, S4L2-SD on the four-cylinder units), chosen for mechanical governing and a 22:1 compression ratio that keeps cold-start behaviour predictable. In this case the trailing IV is the emission stage of the engine fitted, not a different alternator. The frame number is a direct read of the rating: 12 in the code, 12 kVA on the plate, so the label and the data agree.

Why the kVA is bigger than the kW. This is a three-phase set rated at 0.8 power factor, so 10 kW standby corresponds to 12 kVA and the two figures differ by exactly the reactive component the alternator has to carry. Quoting only the kW understates the copper and the switchgear: cables, breaker and busbar all size on the 12 kVA and the 17.3 A line current, while the engine only ever sees the 10 kW. That split is the most common source of undersized installations on three-phase sets in this class.

Standby and prime are two different machines in one frame. ISO 8528 defines standby (ESP) as the maximum a set may deliver for up to 200 hours a year on a varying load, with no overload capability, and prime (PRP) as the continuous rating under a varying load for unlimited hours with a 10 per cent overload window. This set is 10 kW / 12 kVA standby and 9 kW / 11 kVA prime, so the gap between the two, 1.2 kW, is the margin the engine keeps for overload and for altitude and temperature derating. If the load runs for days rather than hours, quote against prime and treat the standby figure as a peak that must not be sustained.

What the nameplate means once it is wired in. At 12 kVA this set pushes 17.3 A down each line on a 400 V three-phase supply, and 15.3 A at the prime rating. Those currents, not the kVA figure, are what the switchgear and the cable have to survive: the outgoing breaker should be a 25 A frame device set to trip above 19.1 A, and the run from the alternator terminals to the first panel should be 6 mm2 copper per phase for a normal 20 to 30 m span. On a single-phase set the same current sits on two conductors instead of three, so the cable is heavier for the same kVA, which is the hidden cost of going monophase above about 15 kVA.

The engine behind the badge. SDMO is engine-agnostic by design and picks the diesel per frame. On the T and K ranges in this class that engine is Mitsubishi: the S3L2-SD three-cylinder at 1.32 L on the smaller units and the S4L2-SD four-cylinder at 1.50 L as the rating climbs, both naturally aspirated, mechanically governed and running a 22:1 compression ratio. Mechanical governing is the point: it holds frequency without an electronic map, which is what makes these sets tolerant of dirty fuel and of long periods between runs. The trade is that the fuel curve is fixed, so light-load fuel economy is worse than a common-rail engine of the same output.

Who actually owns SDMO now. Kohler bought SDMO in 2005 and the product has been Kohler-SDMO since; Kohler itself moved to Platinum Equity in 2024. In practice that means the set you buy today is a French-designed package (Brest is the main plant, with assembly also in Spain, India and Brazil) carrying a Kohler controller and a Kohler-owned warranty chain. It also means the K-prefix and T-prefix frames share the same alternator tooling, so a K9 and a T9KM differ mainly in winding and canopy rather than in core hardware.

Emissions. The IV suffix marks the engine emission stage. On this frame that is an export-tier build: it is not EPA certified for the United States or Canada and is sold for markets that follow the older Stage IIIA / Tier 3 limits. Mechanically it is the simpler machine, with no after-treatment in the exhaust, which is why it is cheaper and why it tolerates long idle periods better than a Tier 4 Final set. If the destination is North America, quote the T4F or T4i version instead.

What the IV build actually is. The trailing IV on T12K IV is the emission stage of the engine, not a different alternator or a different frame. On this platform IV marks the export-tier calibration: the engine is built to the older Stage IIIA equivalent limits, it carries no diesel particulate filter and no diesel oxidation catalyst, and it is therefore not certified for sale into the United States or Canada. That single fact drives most of the practical differences a buyer feels. There is no after-treatment to load up, so the set tolerates short runs and long idle periods without the exhaust back-pressure penalty that a Tier 4 Final machine suffers. There is no regeneration cycle to interrupt, so nothing on the set will suddenly command a higher load while it burns off soot. There is also no after-treatment service interval, which means the maintenance bill over ten years is essentially oil, filters and coolant. The trade is regulatory: if the destination is a regulated market, this exact machine cannot be shipped there, and no amount of paperwork changes that. The sibling II build of the same frame sits on the other side of that line.

The alternator end. The machine is a brushless, four-pole, single-bearing alternator direct-coupled to the engine flywheel housing, insulated to class H and protected to IP23. Regulation is by AVR at plus or minus one per cent steady state with total harmonic distortion under three per cent, which is clean enough for a UPS input but not clean enough to skip a filter in front of a sensitive analyser. Single bearing means the alternator has no bearing of its own on the drive end: it relies on the engine flywheel, which is why alignment and flywheel housing condition matter at every overhaul.

Control and protection. The standard panel gives manual and automatic modes, LCD metering of phase voltage, line current, kW, pf, kWh and engine oil pressure, coolant temperature and fuel level, plus a Modbus RTU port on RS485 for a building management system. Protection covers over-speed, low oil pressure, high coolant temperature, over and under voltage, over and under frequency, over-current and phase sequence, with the last twelve events held in a rolling log. That event log is the single most useful diagnostic on the machine: when a set trips at three in the morning, the log tells you which of the eight protections opened first.

Canopy and noise. The open skid build is the machine on a base frame with the radiator exposed, suitable for a plant room or a covered compound. The soundproofed canopy drops the one-metre level to roughly 68 to 72 dB(A) and is the version most export buyers take, because it also weatherproofs the set and lets it stand outdoors. Containerised and trailer-mounted builds use the same core machine with a different envelope, so the electrical data on this page holds across all four.

Fuel and runtime. At full load the engine burns about 3.1 L/h, at 75 per cent about 2.5 L/h and at half load about 2.1 L/h. The litres-per-kWh figure is worst at part load (0.42 L/kWh at half load against 0.31 at full load), which is the counter-intuitive part of sizing: a set run at half load burns more fuel per unit delivered than the same set run hard. On a 50 L base-frame tank that works out to roughly 20 hours at 75 per cent load, and on a 100 L tank roughly double. For anything above eight hours of continuous running, plan a bulk tank with a day tank and a transfer pump rather than relying on the base frame.

Where this rating actually fits. A 10 kW three-phase set is the entry point for light industrial and commercial standby: a workshop with a few machines, a cold store, a small hotel, a telecom site, a water treatment pump set. Three phase at this rating means motors start properly and the cable is a third of the copper of the single-phase equivalent. The constraint is balance: keep the phase-to-phase imbalance under 20 per cent, because an unbalanced load derates the alternator faster than an overload does.

Parallel operation and transfer. Below about 30 kVA, paralleling is rarely worth the control complexity: two sets need load-sharing governors, synchronising hardware and a common switchgear panel, and the cost of that exceeds the cost of simply buying one larger set. What this rating does need is a proper transfer arrangement: a manual changeover switch if the site is attended, an automatic transfer switch with a mains-failure sensor if it is not. The set itself accepts a remote start signal on a two-wire dry contact, which is all an ATS needs.

Maintenance that actually gets done. Oil and oil filter at 250 hours or annually, whichever comes first; fuel filter and air filter at 500 hours; coolant condition checked annually and changed at two years; valve clearance checked at 1,000 hours. The item most often skipped is the load bank test: a set that runs monthly on a light load will wet-stack and glaze the bores, and the first time it sees a real load it will smoke and under-perform. Run it at 75 per cent load for an hour every quarter, and record the exhaust temperature, because that is the number that tells you the engine is healthy.

Sizing it against a cold store. A cold store is the classic case where the load is almost entirely motor starting. The compressors are hermetic or semi-hermetic, they start against head pressure unless the system has a pump-down cycle, and each start can pull five times running current for half a second. On a 12 kVA set the practical limit is one compressor starting at a time with the evaporator fans already running, which is about 6.2 kW of steady load plus the start. If the store has two compressors that can start together, either interlock them or move up a frame. The other factor is the duty: a cold store runs the set for hours, not minutes, so quote against the prime rating of 9 kW rather than the standby figure, and check that the fuel tank gives the runtime the store needs to reach the next delivery.

Earthing and neutral arrangement. The alternator on this set is a four-wire star machine, so the neutral is available and the earthing arrangement is a decision, not a default. For a set operating as a standby source with a changeover that switches the neutral, the set neutral is bonded to earth at the set and the installation is treated as a separately derived system. For a set operating in parallel with the mains, or through a changeover that does not switch the neutral, the bonding has to follow the installation's existing arrangement or the residual current protection will not work. This is the item to get a competent electrician to confirm in writing, because getting it wrong is a shock hazard rather than an inconvenience.

Coolant loss and the overheat chain. Overheating on a set this size is almost never the thermostat alone. The chain is: a slightly low coolant level, a partially blocked radiator core from dust or insects, a fan belt that is a little slack, and a hot day. Each is trivial and the combination shuts the set down at the worst moment. Check the coolant level weekly rather than monthly, clean the radiator fins with compressed air from the fan side, and replace the belt at the interval rather than when it looks bad. If the set has a low-coolant-level sensor, test it at every service, because a failed sensor is invisible until it matters.

Delivery, unloading and site access. A 12 kVA set in a canopy is heavy enough that it cannot be manhandled, and the most common delivery problem is that the site has no way to lift it off the truck. Confirm the weight, confirm the lifting points, and confirm that a forklift or a crane can reach the final position before the truck arrives. A set that has to be dragged into place arrives with a bent base frame and a misaligned alternator. On a trailer-mounted build, confirm the towing vehicle's rating and the coupling type, because a trailer that cannot be towed legally is a static set with extra cost.

Noise and vibration, measured rather than claimed. Sound level on a canopy set is quoted at one metre and at seven metres, and the two numbers differ because sound falls off with distance: roughly 68 to 72 dB(A) at one metre becomes about 58 dB(A) at seven. What the datasheet does not tell you is the tonality, and a set with a pronounced low-frequency component is more annoying at a boundary than a louder but smoother one. Vibration is a separate issue and it is measured in millimetres per second at the alternator bearing housing; anything above about seven is worth investigating, and the usual cause is a collapsed anti-vibration mount or a misaligned coupling. Ask for both numbers at commissioning and record them, so that a change two years later has a baseline.

Where it sits in the range. Within the same Kohler-SDMO T family at 50 Hz, one step up is the T11U IV at 11 kW / 14 kVA. The step between frames is a different engine displacement and a different alternator core, not a re-rated plate, so the price step is real rather than administrative.

How to order it. Quote five things together and the factory cannot get it wrong: the model (T12K IV), the standby and prime rating, the voltage and frequency (400 V, 50 Hz), the phase (three phase), and the enclosure (open skid, soundproofed canopy, containerised or trailer). Add the emission tier if the destination is regulated. Anything else, including the controller variant, the alternator brand and the fuel tank size, is a build option rather than a different machine.

Frequently Asked Questions

What are the standby and prime ratings of the T12K IV?

Standby output is 10 kW / 12 kVA (ESP), prime output is 9 kW / 11 kVA (PRP). The standby (ESP) figure is the maximum the set can carry for the duration of a mains failure and is not meant for continuous running. The prime (PRP) figure is what it can hold indefinitely at a varying load. Match the rating to the duty the set will actually see — running a standby-rated machine as prime voids the warranty.

What voltage and frequency does the T12K IV output?

The T12K IV is wound for 400 V, 50 Hz, three phase, 4-wire (star), running at 1500 rpm. Voltage and frequency are fixed when the set is built, so confirm the site supply before the order is released. Other voltages and both 50 Hz and 60 Hz builds are available on the same frame.

Which engine drives the T12K IV?

The T12K IV is powered by a Mitsubishi S3L2-SD engine from KOHLER. Engine and alternator are matched on the test bed, so the set reaches its rating without derating.

What is the fuel consumption of the T12K IV?

Fuel consumption is 3.1 L/h (0.31 L/kWh) at 100% load, 2.5 L/h at 75% load and 2.1 L/h at 50% load. These are measured figures on the standard build at those load points; real consumption shifts with load profile, ambient temperature and fuel quality. Send the expected daily running hours and average load if you want a duty-cycle estimate.

How long will the T12K IV run on a full tank?

Runtime is 20 hours on a 50 L base tank. Tank capacity can be increased on request, and runtime scales directly with it against the consumption figures above.

How loud is the T12K IV?

Sound pressure is 71 dB(A) @ 1 m, 58 dB(A) @ 7 m on the soundproofed build. An open skid set is considerably louder and needs either an acoustic canopy or a separate plant room to meet site noise limits.

What enclosure options are available for the T12K IV?

The T12K IV is available as open skid, weatherproof silent canopy, containerised or mobile trailer. Enclosure choice changes footprint, weight, noise level and price, so specify it with the enquiry and the quotation will match the build.

What controller and alternator are fitted to the T12K IV?

The T12K IV ships with an APM303 (TELYS optional) and an AT00350T alternator. Both are build options — alternative controllers and alternator makes can be specified when the order is placed.

How stable is the voltage output of the T12K IV?

On this set, voltage is held by an AVR, +/- 1% steady state, THD < 3% and the machine is built with Class H insulation, IP23 protection. That grade of regulation suits motors, pumps and most electronic loads; for sensitive IT or medical equipment, specify the higher-grade controller option.

What protection does the T12K IV have?

The controller trips on over-speed, low oil pressure, high coolant temperature, over/under voltage, over/under frequency, over-current, phase sequence. These shutdowns stop the set before damage occurs, which is what makes an unattended standby installation safe to leave running.

What warranty comes with the T12K IV?

Warranty is 2 years or 2,000 hours, international coverage. It applies to the set as configured — running outside the rated duty, using non-specified fuel or skipping scheduled service will void it.

How do I get a firm price for the T12K IV?

Send the model (T12K IV), the duty (standby or prime), voltage and frequency, phase, and the enclosure type you need. Jinjia Power quotes against a confirmed configuration rather than a list price, so the figure you receive matches the machine that ships. Typical lead time is 20–30 days for units up to 1000 kW and 30–45 days above that.