Status: IN STOCK, Same day shipping Worldwide available | Brand New, 1 Year International Warranty
* Contact us for pricing and full specifications
| SKU | GRT7-TH4 R6 10A |
| Brand | GRAMEYER |
| Model Number | GRT7-TH4 R6 10A |
| Regulator Type | Analogue Automatic Voltage Regulator |
| Excitation System | Self-excited, shunt fed |
| Sensing Input | 160-300 Vac or 320-600 Vac single-phase sensing |
| Power Input | 170-300 Vac single-phase or two-phase, 50 / 60 Hz |
| Output Voltage | 76.5-126 Vdc |
| Continuous Field Current | 5 A rated on TH4 and TH4 E, 7 A rated on TH4 P and TH4 PE |
| Forcing Current | 7 A for 10 s on the 5 A builds, 10 A for 10 s on the 7 A builds |
| Field Resistance (Min) | 6-50 ohm at 20 degC |
| Regulation Accuracy | 0.5 per cent static |
| Response Time | Dynamically adjustable from 8 to 500 ms |
| Frequency Range | 50 / 60 Hz |
| Under-Frequency Protection | Adjustable under-frequency protection by trimmer |
| Voltage Adjustment | Internal trimmer over the full range, external adjustment to -30 per cent of sensing voltage |
| Paralleling / Droop | Reactive droop, 5 A CT for parallel operation with a PAR/5 controller |
| Build-Up Voltage | Builds up from residual voltage |
| Thermal Drift | Low thermal drift |
| Operating Temperature | -20 to +60 degC |
| Storage Temperature | -40 to +85 degC |
| Protection Features | Under-frequency, over-excitation, EMI filtered input |
| Compatible Alternators | Leroy Somer, Stamford, Marelli and Mecc Alte alternators with 6-50 ohm fields |
| Mounting | Panel or terminal-box mount |
| Lifecycle Status | In production |
| Availability | IN STOCK, Same day shipping Worldwide available |
| Condition | Brand New, 1 Year International Warranty |
| Warranty | 1 Year International Warranty |
Position in the range. The GRT7-TH4 R6 10A sits in the GRAMEYER regulator family carrying the designation Analogue Automatic Voltage Regulator. Its place is defined by the field current it can hold, 5 A rated on TH4 and TH4 E, against the field resistance it can drive, 6-50 ohm at 20 degC, at 0.5 per cent accuracy over -20 to +60 degC. Where a machine falls outside either of the first two figures, a different member of the same family is the correct answer rather than a workaround.
Excitation architecture. Self-excited, shunt fed. That single sentence decides most of the regulator's behaviour in a fault: whether the field survives a close-up short circuit, whether the machine builds up from residual voltage on its own, and how much the terminal voltage dips when a large motor starts on the same bus. If the machine will not hold voltage at all, disconnect the field and measure the sensing voltage first. That one reading separates a sensing fault from a field fault.
Sensing. 160-300 Vac or 320-600 Vac single-phase sensing. The sensing circuit is the regulator's only view of the outside world, so its wiring matters as much as its specification. A voltage error introduced by a loose terminal or a long run of untwisted cable is indistinguishable, from the regulator's point of view, from a genuine voltage error on the alternator. Static accuracy is measured on a resistive load at constant frequency. Real loads and real governors are neither, so treat the figure as a comparison between boards rather than a promise.
Power stage and field drive. Power input 170-300 Vac single-phase or two-phase, 50 / 60 Hz, output 76.5-126 Vdc. Field current rating 5 A rated on TH4 and TH4 E, forcing capability 7 A for 10 s on the 5 A builds, 10 A for 10 s on the 7 A builds, field resistance window 6-50 ohm at 20 degC. These are not independent numbers: the output voltage ceiling and the field resistance together set the maximum current the board can actually deliver, and the continuous rating is only reachable at the low end of the resistance window. Static accuracy is measured on a resistive load at constant frequency. Real loads and real governors are neither, so treat the figure as a comparison between boards rather than a promise.
Accuracy and response. 0.5 per cent steady-state accuracy, Dynamically adjustable from 8 to 500 ms, thermal drift Low thermal drift. In practice the accuracy figure is the least interesting of the three. What an operator notices is recovery after a load step, which is governed by response and by available forcing current, and what a maintenance engineer notices after two years is drift, which is governed by the reference circuit and the ambient temperature inside the terminal box. Counterfeit regulators are a real problem on the widely copied boards. Buy from a source that will state where the board was made.
Frequency behaviour. Rated for 50 / 60 Hz, with Adjustable under-frequency protection by trimmer. The frequency-sensitive function exists to protect the prime mover, not the alternator: as engine speed falls the regulator reduces excitation so the alternator stops demanding torque the engine cannot supply. Without it, an overloaded engine is dragged down until it stalls, and the alternator is blamed for a fault that belongs to the fuel or governor system. Terminal boxes are hot, dirty and vibrating. Anything mounted inside one should be judged on how it behaves in year eight, not on how it reads on the bench.
Paralleling. Reactive droop, 5 A CT for parallel operation with a PAR/5 controller. On a single set this circuit does nothing. On two or more sets it is the only thing that stops the machines from exchanging reactive power in a slow oscillation, and it is the first place to look when a parallel installation shows a circulating current that nobody can explain. A voltage that is correct at no load and low at full load is almost never an accuracy problem. It is a current limit, a resistance problem or a cable problem.
Protection built into the regulator. Under-frequency, over-excitation, EMI filtered input. These functions protect the alternator and the regulator, not the installation. Downstream protection, loss of mains and reverse power all belong to the controller, and a site that relies on the AVR for them is a site that will eventually trip in a way nobody can explain. Counterfeit regulators are a real problem on the widely copied boards. Buy from a source that will state where the board was made.
What it fits. Leroy Somer, Stamford, Marelli and Mecc Alte alternators with 6-50 ohm fields. Lifecycle status: In production. Both halves of that sentence matter at order time. A board that fits perfectly but has been discontinued is a different commercial decision from one that fits and is in current production, and the price difference rarely reflects the difference in risk. A voltage that is correct at no load and low at full load is almost never an accuracy problem. It is a current limit, a resistance problem or a cable problem.
Field notes on this model. The GRT7-TH4 is the most widely fitted Grameyer board and it comes in four build variants: TH4 at 5 A rated, TH4 P at 7 A rated, TH4 E at 5 A rated with a +/-9 Vdc analogue input, and TH4 PE at 7 A rated with the analogue input. The analogue input is what lets the regulator follow a power factor controller or a remote voltage trimmer, so the E and PE versions are the ones specified on paralleled and marine installations. All four carry CSA approval.
Where this regulator does not belong. A GRT7-TH4 R6 10A is a voltage regulator, not a protection relay and not a governor interface. If the site needs loss-of-mains detection, reverse power protection or synchronising, those functions live in the controller, not here. Expecting the AVR to carry them is how installations end up with a set that holds voltage beautifully and still trips the site on a mains failure.
Mounting orientation and cooling. Most AVR boards are convection cooled and assume the heatsink fins are vertical. Mounting a GRT7-TH4 R6 10A flat on its back inside a sealed box shortens its life even though the ambient temperature reads acceptable, because the local air around the thyristor is far hotter than the box average.
Paralleling setup. With two sets on the bus, adjust droop until reactive load divides in proportion to machine rating, then check it again at half load. A droop setting that looks right at full load and wrong at half load is usually a CT ratio error rather than a regulator fault.
Temperature drift of the field. Copper rises about 0.4 per cent in resistance per degC, so a field that measures 12 ohm cold will measure around 15 ohm at a 70 degC winding temperature. A regulator set up on a cold machine and never re-checked will therefore be running at a different operating point every time the season changes, and the symptom is a voltage that is correct in winter and low in summer.
Voltage drifts with ambient temperature. If the voltage is correct cold and low hot, the thermal drift of the regulator and the temperature coefficient of the field are adding up in the same direction. The GRT7-TH4 R6 10A is specified at 0.5 per cent static; a drift of a couple of per cent over a fifty degree swing is normal for an analogue board and is not a fault.
Delivery and packing. Regulators are static-sensitive assemblies and should arrive in a sealed bag with foam, not loose in a box with a heatsink. Inspect on arrival and photograph the packaging before opening if there is any sign of crush damage.
What the customer is actually buying. When a regulator is quoted as a replacement, the buyer is not purchasing a circuit board. They are purchasing the certainty that the set will hold voltage on the next load step. On the GRT7-TH4 R6 10A that certainty comes from the combination of 5 A rated on TH4 and TH4 E, 7 A rated on TH4 P and TH4 PE continuous field current and the Dynamically adjustable from 8 to 500 ms response, and it disappears the moment the field resistance drifts outside the window the board was set up for.
Fusing. Fit the fuse the manual specifies and nothing larger. A bigger fuse does not protect the regulator better, it protects it later. On a GRT7-TH4 R6 10A the fuse is there to clear a field short before the thyristor is destroyed, and a 20 A fuse in place of an 8 A one turns a cheap board replacement into a rewind.