Status: IN STOCK, Same day shipping Worldwide available | Brand New, 1 Year International Warranty
* Contact us for pricing and full specifications
| SKU | GRTD-1100 |
| Brand | GRAMEYER |
| Model Number | GRTD-1100 |
| Regulator Type | Digital Automatic Voltage Regulator |
| Excitation System | Self-excited or PMG |
| Sensing Input | Single-phase or three-phase RMS sensing |
| Power Input | 170-300 Vac, 50 / 60 Hz |
| Output Voltage | Up to 126 Vdc |
| Continuous Field Current | 15 A class on the 2000 series |
| Forcing Current | Forcing limited |
| Field Resistance (Min) | 6-50 ohm |
| Regulation Accuracy | 0.5 per cent or better |
| Response Time | Digital, configurable |
| Frequency Range | 50 / 60 Hz |
| Under-Frequency Protection | Programmable volts-per-hertz curve |
| Voltage Adjustment | Internal trim potentiometer |
| Paralleling / Droop | Reactive droop, configurable |
| Build-Up Voltage | Builds up from residual voltage |
| Thermal Drift | Low thermal drift |
| Operating Temperature | -20 to +60 degC |
| Storage Temperature | -40 to +85 degC |
| Protection Features | Over-excitation, loss of sensing, over-temperature |
| Compatible Alternators | Mid and large frame alternators |
| Mounting | Panel or terminal-box mount |
| Lifecycle Status | In production |
| Availability | IN STOCK, Same day shipping Worldwide available |
| Condition | Brand New, 1 Year International Warranty |
| Warranty | 1 Year International Warranty |
What the GRTD-1100 is. A Digital Automatic Voltage Regulator built by GRAMEYER for brushless excitation systems. On paper the specification is a list; in service it is a set of limits. The current the board will hold indefinitely is 15 A class on the 2000 series; the field resistance window it will drive without exceeding its output voltage is 6-50 ohm; the tightest voltage band it can maintain is 0.5 per cent; and the ambient range in which all of that remains true is -20 to +60 degC.
Excitation architecture. Self-excited or PMG. That single sentence decides most of the regulator's behaviour in a fault: whether the field survives a close-up short circuit, whether the machine builds up from residual voltage on its own, and how much the terminal voltage dips when a large motor starts on the same bus. Never flash a field through the regulator. Disconnect the board, flash the field directly, then reconnect. Flashing through the AVR is how a working board becomes a failed board.
Sensing. Single-phase or three-phase RMS sensing. The sensing circuit is the regulator's only view of the outside world, so its wiring matters as much as its specification. A voltage error introduced by a loose terminal or a long run of untwisted cable is indistinguishable, from the regulator's point of view, from a genuine voltage error on the alternator. A voltage that is correct at no load and low at full load is almost never an accuracy problem. It is a current limit, a resistance problem or a cable problem.
Power stage and field drive. Power input 170-300 Vac, 50 / 60 Hz, output Up to 126 Vdc. Field current rating 15 A class on the 2000 series, forcing capability Forcing limited, field resistance window 6-50 ohm. These are not independent numbers: the output voltage ceiling and the field resistance together set the maximum current the board can actually deliver, and the continuous rating is only reachable at the low end of the resistance window. Never flash a field through the regulator. Disconnect the board, flash the field directly, then reconnect. Flashing through the AVR is how a working board becomes a failed board.
Accuracy and response. 0.5 per cent steady-state accuracy, Digital, configurable, thermal drift Low thermal drift. In practice the accuracy figure is the least interesting of the three. What an operator notices is recovery after a load step, which is governed by response and by available forcing current, and what a maintenance engineer notices after two years is drift, which is governed by the reference circuit and the ambient temperature inside the terminal box. Field resistance is a temperature-dependent number. A reading taken on a cold morning and a reading taken after an hour at load are both correct and both different.
Frequency behaviour. Rated for 50 / 60 Hz, with Programmable volts-per-hertz curve. The frequency-sensitive function exists to protect the prime mover, not the alternator: as engine speed falls the regulator reduces excitation so the alternator stops demanding torque the engine cannot supply. Without it, an overloaded engine is dragged down until it stalls, and the alternator is blamed for a fault that belongs to the fuel or governor system. An alternator that has been rewound needs its field resistance re-measured, because a rewind commonly moves it by ten to twenty per cent in either direction.
Paralleling. Reactive droop, configurable. On a single set this circuit does nothing. On two or more sets it is the only thing that stops the machines from exchanging reactive power in a slow oscillation, and it is the first place to look when a parallel installation shows a circulating current that nobody can explain. A voltage that is correct at no load and low at full load is almost never an accuracy problem. It is a current limit, a resistance problem or a cable problem.
Protection built into the regulator. Over-excitation, loss of sensing, over-temperature. These functions protect the alternator and the regulator, not the installation. Downstream protection, loss of mains and reverse power all belong to the controller, and a site that relies on the AVR for them is a site that will eventually trip in a way nobody can explain. Where a board has been superseded, the replacement usually fits the same footprint but not the same terminal numbering. Read the drawing, do not read the old wiring.
What it fits. Mid and large frame alternators. Lifecycle status: In production. Both halves of that sentence matter at order time. A board that fits perfectly but has been discontinued is a different commercial decision from one that fits and is in current production, and the price difference rarely reflects the difference in risk. A voltage that is correct at no load and low at full load is almost never an accuracy problem. It is a current limit, a resistance problem or a cable problem.
Field notes on this model. The GRTD range is Grameyer's digital line. The 2000 series variants, C15A, E15A, ES15A and ESCM15A, differ in the sensing arrangement, the communications option and whether the 15 A power stage is fitted, so the suffix has to be matched to both the alternator and the panel wiring. The 1100 is the smaller digital board for mid-size machines.
Where this regulator does not belong. A GRTD-1100 is a voltage regulator, not a protection relay and not a governor interface. If the site needs loss-of-mains detection, reverse power protection or synchronising, those functions live in the controller, not here. Expecting the AVR to carry them is how installations end up with a set that holds voltage beautifully and still trips the site on a mains failure.
Power and sensing are not the same circuit. The power input on a GRTD-1100 can come from a different winding from the sensing input, and on PMG machines it always does. Wire them as two separate circuits, fused separately, and label both. The single most expensive mistake on a PMG set is landing the sensing leads on the PMG supply, which gives the regulator a voltage reference that rises with speed and produces a set whose voltage tracks engine rpm.
Bench test before installation. Where a spare board is available, test it on the bench with a variable AC supply into the power input and a resistor bank as the field load. A board that cannot hold a steady output into a resistor will not hold it into an exciter either, and finding that out on the bench costs nothing.
The field resistance check. Measure the exciter field with the regulator disconnected and the machine stopped, then measure again after a run. Cold resistance is what the board sees at start-up; hot resistance is what it sees at full load. The GRTD-1100 is specified with a minimum of 6-50 ohm, and the real question is not whether the measured value is above that figure but whether the forcing current at that resistance still reaches the level the alternator needs to recover from a load step.
Do not overlook the obvious. Before condemning a regulator, confirm the engine is actually at rated speed. A set running five per cent slow will show low voltage on any board, and replacing the AVR will not fix a governor.
Lifecycle status. If the board being replaced is discontinued, price the current replacement at the same time as the old-stock option. On a machine that is going to run for another ten years the current production board is almost always the cheaper decision even when the old stock is available.
Where this board earns its place. The GRTD-1100 is normally the answer when a GRAMEYER machine has lost regulation and the original board is either unavailable or priced like a small car. What decides the fit is not the brand name on the cover but three numbers: the field resistance window, the continuous field current, and the sensing voltage the machine actually delivers at the AVR terminals. Get those three right and the regulator behaves; get any one of them wrong and the symptom usually looks like a mechanical fault rather than an electrical one.
Field cable sizing. The field circuit carries DC at low voltage and high current, so volt drop matters more than ampacity. Size the cable so that the drop at 15 A class on the 2000 series stays under about one volt, and torque the terminals to the manufacturer figure. A field circuit that loses half a volt in the cable is a regulator that cannot reach full forcing when the load steps.
Jinjia Power Equipment Co., Ltd | Address: No.737, Guanzhang Road, Liaobu Town, Dongguan, China
Phone: 86-13553838770 | 86-0769-89610677 | info@jinjiadongli.com
Jinjia Power, Quality Assured